Product description
Scope of delivery of the air-termination rods with internal conductor:
– Insulated air-termination rod with side exit
– Internal connection element (type isCon
®
IN connect)
– Potential connection element (type isCon
®
IN PAE)
– Brief instructions
Scope of delivery of the air-termination rods with external conductor:
– Insulated air-termination rod with bottom exit
– Brief instructions
3 4
System accessories for fastening
Air-termination rod stands (see section 3.4.1) or supports for wall or pipe
mounting (see section 3.4.2) can be used to fasten the isCon
®
air-temin-
ation rods. In addition, the system offers special holders for the isCon
®
conductor (see section 3.4.3).
3 4 1
Air-termination rod stand
Figure 6:
Air-termination rod stand with concrete blocks
The isCon
®
system contains folding air-termination rod stands of different
sizes, to allow the isFang air-termination rods to be mounted on flat roofs,
for example. The tripod air-termination rod stands allow the erection of the
air-termination rods without penetrating the building structure with bolts/
anchors.
Instead, the air-termination rod stands are weighed down with FangFix
concrete blocks. The number of blocks required is dependent on the
height of the air-termination rod and the wind speed zone.
Note:
You can find further information on wind speed zones in the OBO TBS
lightning protection guide (order no.: 9131970) and national directives.
The air-termination rod stand can compensate for a slope in the roof
surface of up to 5° (see also Figure 48 on page 44). To protect the
roof surface, it may be wise to place a protective film under the concrete
blocks of the air-termination rod stand. We recommend contacting the
roofer about this.
Scope of delivery of the air-termination rod stand:
– Tripod air-termination rod stand
– Crossbar for potential connection with bolt, nut and lock washer
– Brief instructions