Installing the isCon® system
When mounting equipotential bonding elements (clips, clamps):
• Using a cable knife ("jokari knife"), remove the light grey jacketing in
the contact area along a length of 100 mm.
100 mm
> 1.5 mm
1.5 mm
Figure 18:
Releasing the light grey outer jacketing within the cable routing
Note!
The jacketing of the light grey isCon
®
conductor can be painted. It does
not possess any electrical properties which could be at risk from paint.
5 1 2
Revealing the copper core for connection
• Using the stripping tool isCon
®
stripper 2, adjust the stripping length to
25 mm.
25 mm
Figure 19:
Adjusting the stripping length
• Insert the isCon
®
conductor into the cutting head and, with slight pres-
sure, turn the handle in a clockwise direction until the preset length of
the insulation has been cut off.
25 mm
Figure 20:
Cutting the insulation