Installing the isCon® system
Preparing the isCon conductor
• When using the isCon
®
ProPI 75 LGR:
Using a cable knife, remove the grey cable jacketing to a length of
50 mm (see also “„5.1 Cutting and removing the insulation of the
isCon® conductor“ on page 28).
• Mount the connection element (Figure 39 No.
3
) on the isCon
®
conductor as described in sections “„5.1.2 Revealing the copper core
for connection“ on page 29 and “„5.2 Mounting the isCon® connect
connection elements“ on page 30.
Only for the light grey isCon
®
conductor:
To connect the potential connection element, the light grey jacket in the
contact area must be removed.
ATTENTION
Risk of damage!
The black, weakly conductive jacket may not be removed, as otherwise
the connection to the building's equipotential bonding can be interrupted.
In the case of the grey cable jacket, maintain a maximum cutting depth of
1.5 mm.
• Measure 1,500 mm from the bottom edge of the isCon
®
connect con-
nection element.
• Remove 50 mm of the grey cable jacket with a cable knife.
50 mm
50 mm
1,500 mm
> 1.5 mm
1.5 mm
Figure 40: