39 | EN
Screw-on cable tray systems
Mounting
Without connector, 400–600 mm cable tray width
Bends with a width of 400 mm or more have connector perforation.
Bends with a side height of 35 or 60 mm are mounted with RLVK 35/60
straight connectors and a joint plate. Bends with a side height of 85 or
110 mm are mounted with RLVL 85/110 straight connectors and a joint
plate. The straight connector and the joint plate are screwed on with FRS
M6 truss-head bolts and combination nuts.
Fig 41:
Pre-drilling the mounting holes for the joint plate
1. Pre-drill unperforated cable trays for the mounting of the joint plates.
2. Insert RLVK or RLVL straight connectors on the inner side of the rail.
Fig 42:
Screwing on the straight connectors and joint plates
3. Screw on the straight connector.
4. Screw on the joint plates.