43 | EN
Screw-on cable tray systems
Mounting
Without connector, 400–600 mm cable tray width
Add-on tees with a width of 400 mm or more have connector perforation.
Add-on tees with a side height of 35 or 60 mm are mounted with RLVK
35/60 straight and angle connectors. Add-on tees with a side height of
85 or 110 mm are mounted with RLVL 85/110 straight and angle connec-
tors. The straight and angle connectors are screwed on with FRS M6
truss-head bolts and combination nuts.
W+2x1
50
B
150
150
Fig 48:
Notching out a cable tray rail
1. Notch out the cable tray rail with the dimension = W+2x150 mm.
Fig 49:
Mounting the connector and joint plate
2. Pre-drill the connector perforation for the add-on tee and joint plate.
3. Screw the RLVK or RLVL straight and angle connector to the branch-
ing cable tray.
4. Screw the joint plate to the branching cable tray.