47 | EN
Mounting instructions, PYROLINE
®
BSK fire protection duct
Mounting the PYROLINE® Con S BSK with a support system
2. Push the threaded rod
3
through the threaded rod adapter and draw
the drill hole on the ceiling.
3. Drill the drill hole.
4. Screw the bolt tie
2
under the ceiling.
5. Screw the threaded rod into the bolt tie.
6. Secure the threaded rod on the threaded rod adapter with hexagonal
nuts and a washer.
7. Firmly connect the threaded rod adapter with connectors of the duct
trough.
Note!
To insert the cables easily into the ducts later, the nuts on the thread-
ed rod can be slightly loosened, along with those on the threaded rod
adapter. Then unscrew the threaded rod from the bolt tie and temporarily
secure it against slipping with the loosened nuts on the threaded rod
adapter.
8 9
Mounting an end piece
1
2
3
Abb 40:
End piece mounting
The fire protection duct must be tightly closed to prevent smoke gases
from escaping during a cable fire. Open cable ends are closed off with
an end piece suitable for the fire protection duct.
Note!
Sealing strips are already pre-mounted on the end pieces in the factory.
Risk of damage!
When the end piece is screwed on, the edges can chip, making the end
piece unusable. Pre-drill the end piece before mounting.
Note!
Mount the end piece (with the sealing strip
1
) in front of the duct.
1. Mount the end piece
2
in front of the front side with at least 4 coun-
tersunk head screws
3
.
ACHTUNG