Mounting instructions PYROLINE
®
Rapid fire protection duct
EN | 43
Mounting on a support system
6 1 3
Mounting on a support/bracket
With this mounting type, the duct route is supported by brackets (recom-
mended: AW 15..), which, in turn, are fastened to ceiling supports (rec-
ommended: US5 K..). We recommend using the OBO bolt tie, type BZ
12-15-35/110, for ceiling fastening of the support.
We recommend a maximum distance of 100 mm between the support
element and the joint.
• Fasten the duct to the bracket with a combination of M6 bolt, nut and
washer.
After filling with cables, seal the joint between the two ducts with a
combination of a support plate (BSKM-AD 0407, BSKM-AD 0711 or
BSKM-AD 1025) and duct connector (BSKM-VD 0407, BSKM-VD 1025 or
BSKM-VD 0711).
• Screw the support plate to both ducts using the four self-tapping
screws contained in the scope of delivery of the support profile.
• Then screw the duct connector to the support profile.
max. 1
m
max. 1
00 mm
Fig 47:
Example for routing on support/bracket
With support/bracket mounting, we recommend using the system compo-
nents shown in Fig. 48.
SKS 10X80 F
AW 15 .. FT
DSK 45 FT
US 5 K .. FT
Fig 48:
Example of support/bracket mounting
To fasten the support to the ceiling, we recommend using two OBO bolt
ties, type BZ 12-15-35/110.