11 | EN
PYROPLUG
®
MagicBox
Installation requirements, PYROPLUG® MagicBox
6 3
Approved assignment
Cables
Electrical cables of all types,
total diameter of the individual cables ≤ 80 mm
Electrical installation pipes (EIP) made of plastic and steel
Pipes according to EN 61386-1/-21/-22
With and without cable assignment max. 21 mm cable diameter; max. EIP Ø
63 mm, bundled up to max. 100 mm
For details, see aBG Z-19.53-2618, Section 2.3.2.3
Cable support systems
Cable trays, perforated and unperforated
Cable ladders
Mesh cable trays
Other assignment
Klimasplit cable combinations consisting of copper pipes up to 22.22 mm with
heat insulation, condensate hose and up to three accompanying cables
For details, see aBG Z-19.53-2618, Section 2.3.6.1
Hydraulic cables with AEROQUIP wire mesh inlay up to 64.3 mm
For details, see aBG Z-19.53-2618, Section 2.3.4
Copper pipes up to 35 mm and PU hard foam insulation WICU eco
For details, see aBG Z-19.53-2618, Section 2.3.5
Hollow conductor cables of the product ranges CELLFLEX, RADIAFLEX and
HELIFLEX of make RFS GmbH, Hanover, and the product ranges HELIAX
and RADIAX of make CommScope Technologies Germany GmbH, Ober-
hausen
For details, see aBG Z-19.53-2618, Section 2.3.2.2