background image

AcquiLite Administration Overview

The AcquiLite should now be available on the local area network for you to access using a web browser such as Internet 
Explorer or Netscape.

Step 1

 - Use your web browser to connect to the AcquiLite by entering

http://192.168.40.50/setup/
Where 192.168.40.50 is the IP address displayed on the on the AcquiLite LCD display.

Step 2

 - When prompted, use the following default login information

Login: admin
Password: admin

Step 3

 - Your web browser should now display the AcquiLite configuration menu. To the left, a list of configuration options 

are available. On the right, a specific configuration page will be shown. The first page is a welcome message with some 
system status information. Proceed with the configuration of the AcquiLite using your web browser.

Step 4 -

 Click on the 

+

 mark next to the Accounts menu. Select the Admin account, and click 'Change Password'. All units 

are shipped with the same factory default password, and it should be changed to prevent unwanted access.

Step 5 -

 Expand the Networking option, and select setup. Verify the addresses are consistent with those in the "Network 

Address Worksheet."

Step 6 -

 Expand the Modbus option, and select "Device List." You should see an entry for the onboard pulse inputs. 

A. Click the device number to the left of the device 250 (onboard pulse inputs). 
B. A page with the current device status and readings will be displayed. Click on the 'configure' button at the bottom of 

the page. 

C. Enter a name for the device in the supplied field. 
D. Change any low and high range alarm settings you may need.  (optional)
E. Click the 'Save' button at the bottom of the page to save your changes. 
F. Repeat these steps for each Modbus device. 

Step 7 -

 Select the Modbus/Setup menu option. Specify the Modbus Loop Name.  This will become the name of the 

AcquiLite. This is the name that will appear on the BMO website service (if subscribed). Specify the data logging period. 
The default is 15 minutes.

Step 8 –

 Decide upon a method of data transfer.  (see section later in this document) . If you select the HTTP/Post method to 

send data to the BMO website, you can configure this by selecting the “LogFileData, Setup/Upload” page.

A. Make note of the AcquiLite serial number. 
B. Select upload options as needed for time of day to upload the data and retry control. 
C. Check the checkbox to allow remote configuration.  This will allow you to reconfigure the AcquiLite from the 

BMO web site without having to connect directly to the AcquiLite. 

D. Specify the "Target address to upload data." This is the website address where the AcquiLite will send the collected 

data. If you have an in-house data collection service, you should enter the address of your data server in this field. 
Obvius also provides a service called Building Manager Online that can collect and report data for you. If you are 
using the BMO service, the target address to upload data should be set to 
http://www.buildingmanageronline.com/upload.php 

E. When configuring the AcquiLite to send data to the BMO site or your own data collection server, the AcquiLite will 

authenticate itself with the server by using the serial number and a password. This password must be supplied here, 
and can be obtained when you subscribe for the BMO service, or by your database administrator. 

F. Click "Apply" to save your changes. 

If you select a manual transfer method, remove (blank out) the target address in the Modbus/Upload Data page.

Page 10

A7810 AcquiLite – Data Acquisition Server

www.

.com

information@itm.com

1.800.561.8187

Summary of Contents for AcquiLite EMB A7810

Page 1: ...cquiLite EMB Data Acquisition Server Obvius LLC Installation and Operation Manual Model A7810 Date Aug 10 2011 Page 1 A7810 AcquiLite Data Acquisition Server www com information itm com 1 800 561 8187...

Page 2: ...r modified outside of Obvius s authorized facilities 4 has not been sold subject to other warranty terms specified at the time of sale and 5 is still owned by the original purchaser This warranty prov...

Page 3: ...17 Troubleshooting Ethernet Problems 18 System Options 18 Status 18 Processes 18 Date and Time 18 Universal Time Is Your Friend 19 System logs 19 Firmware Update 20 Diagnostics 20 Host Lookup 20 Conne...

Page 4: ...rnet 10 100Mbit connection point hub or switch IP address and Netmask check with system administrator Gateway address check with system administrator DNS server address check with system administrator...

Page 5: ...ulse width 10ms Pulse rate option 100hz minimum pulse width 5ms Contact closure threshold 100 to 2 5k user selectable Pulse count values are stored in non volatile memory Isolation2 The RJ45 Ethernet...

Page 6: ...ould be dangerous if wire scraps come into contact with high voltage wires Step 4 Power up and diagnostics A power supply is not provided with the AcquiLite EMB therefore it is up to the installer to...

Page 7: ...gured into the AcquiLite or Dynamic Host Configuration Protocol DHCP address this process assigns an IP address dynamically to the AcquiLite when it is connected to the network from a host DHCP server...

Page 8: ...will be obtained automatically Simply select the Enable DHCP from the first TCP IP configuration menu Step 4 After the address information has been set you must reboot the AcquiLite Select the Previo...

Page 9: ...tems is beyond the scope of this document however A From the Windows start menu select the Settings Network Connections option Double click the Local Area network connection icon in the network folder...

Page 10: ...Repeat these steps for each Modbus device Step 7 Select the Modbus Setup menu option Specify the Modbus Loop Name This will become the name of the AcquiLite This is the name that will appear on the BM...

Page 11: ...ername password for read only access Log information is stored in var log modbus For read write delete access use the login name root and the admin password The three usernames specified are not able...

Page 12: ...ption can be used to configure a Modbus device that is not presently connected to the system add a framework configured device or add a Modbus TCP connected device See the section on manually adding a...

Page 13: ...he bottom of the page several buttons are present Done returns you to the device list page Log File This icon will display a table view of the most recent data in the current log file Use the log file...

Page 14: ...Multiple data points are rotated about every 10 seconds The values on the LCD console are updated when the next log interval occurs Point Config Some devices have configurable point features Most dat...

Page 15: ...ame as any address already listed in the device list page Modbus TCP Gateway IP This option allows the AcquiLite to log data from a remote Modbus device that is attached to the LAN via a Modbus TCP ga...

Page 16: ...only allows control based on the IP address of the system making the request The Modbus TCP protocol does not have provisions for any authentication password or other methods of security By default t...

Page 17: ...n such a way the wireless diagnostics options will be present in the AcquiLite Please refer to the AcquiSuite A8812 or A8810 user manuals for further details on the wireless diagnostic features Networ...

Page 18: ...e NOTE one common mistake is configuring the Laptop IP to the same address as the IP address of the AcquiLite In order for the laptop and AcquiLite to communicate the IP addresses should not be identi...

Page 19: ...is to store data in the database in UTC format and then convert the information when generating a report for the user For example if you wish to draw a graph of KW over Time prompt the user for a date...

Page 20: ...g of the files will be displayed If any firmware updates are available a button to the right will be shown labeled Download The firmware files are asarm cramfs The main AcquiLite firmware file includi...

Page 21: ...ndicated The failure is due to the password not being correct LCD Console The AcquiLite has an LCD console and two push buttons labeled Menu and Select These can be used to configure some of the basic...

Page 22: ...respond to ping requests This test does not verify if the DNS servers can actually resolve DNS names to IP addresses For a more complete test use the Connection Test web page in the AcquiLite diagnost...

Page 23: ...he log file name starts with mb xxx where xxx is the Modbus device address number One file with the log extension is the file where the most recent data is being stored Other log files have a gz exten...

Page 24: ...file busy 28 No space left on device 32 Broken pipe 52 Invalid Exchange 101 Network is unreachable 110 Connection timed out 111 Connection refused 113 No route to host 129 Illegal Function function wa...

Page 25: ...lly push the log files to your server you must manually delete them To delete log files refer to the FTP method of downloading log files One step detailed in the FTP section is how to delete a log fil...

Page 26: ...re detailed information about the transfer process use the Connection Test page in the Testing Diags menu on the AcquiLite for a full report of the data upload progress Retrieving Data From the AcquiL...

Page 27: ...when data is uploaded Designed for integration with existing energy reporting systems Contact Obvius technical support for further details and sample scripts Removing Data From the AcquiLite When usi...

Page 28: ...he page will be shown on that dialog Simply copy paste this URK into your link The AcquiLite can provide Modbus device data in XML format This feature coupled with browser based AJAX Javascript can pr...

Page 29: ...that is approximately 4 x 4 25 x 2 deep The AcquiLite has 4 mounting holes for use with a 6 screw The drawing above shows the relative position of the mounting holes Page 29 A7810 AcquiLite Data Acqu...

Reviews: