Version 5.2_2022 (January 26, 2022)
11
5.7.
Siphon
The draining of condensation (drip-tray) must be carried out using the siphon provided. This siphon serves
as a water shut-off to prevent possible unpleasant odours and to drain possible excess water from the drip
tray.
5.7.1.
Siphon maintenance
The negative pressure siphon (silicone rubber non-return valve) must be cleaned. Please ensure correct
assembly. See picture.
5.8.
Fan
The air flow through the heat exchangers is provided by directly driven plug fans with EC motors. The fans
are speed-controlled by means of a rotary knob located on the control panel.
The fans are controlled by the PLC and communicate via ModBus.
Because EC motors are used, there is no risk of the fans turning in the wrong direction. Please note that a
leakage current is present.
! CAUTION:
Position number Description
1-2-3
3-piece coupling
4
diaphragm seat
5
Silicone diaphragm
6
Reducing ring 32-25
7
PVC pipe 32 L=40 / L=260
8
PVC elbow 32
9
PVC pipe 25 L=50
10
Hose coupling PVC 32 glue 30 hose
11
Flat ring (rubber)
12
Simplex plug 5/4"