The main switch of the unit must be
switched off and locked at all times
when handling or working on the unit!
! CAUTION:
After switching off the supply voltage,
it will take some time before the fans
have come to a complete stop. Please
bear this in mind when opening the
service doors/hatches!
5.8.1.
Fan maintenance
Clean the fan impeller if necessary. Make sure that the balancing weight on the impeller is not moved or
removed.
Check the impeller for imbalance. The imbalance is noticeable when the Aqua Cool vibrates noticeably on
the outside. In this case, remove the fan and have it rebalanced. It is also possible to have this done on site
by a specialised company.
Check wiring.
The motor is maintenance-free.
5.9.
Housing
The housing of the Aqua
Cool
consists of double-walled (sandwich) panels made of Sendzimir-galvanised
sheet steel 1 mm thick, with an internal and external 100µ powder coating in RAL7035 as standard.
The housing has a wall thickness of approximately 50 mm. The insulation consists of expanded insulation
material and is fully bonded to the inner and outer sheets of the sandwich panel.
The housing has 2 connections for air inlet and 2 connections for air outlet. All connections are around 500
mm.
5.9.1.
Maintenance of housing
The housing must be inspected periodically, both internally and externally, and if necessary cleaned with a
non-aggressive cleaning agent. Touch-up or reapply damaged coating.
Check all inspection doors/hatches for proper sealing and if necessary treat the rubbers against sticking and
replace if damaged. Check the roof for damage and leaks and touch it up if necessary.
5.10.
Control panel
The control panel is located under the switch panel (via the door under the switch panel).