background image

16 

FAN SPEED—

The operator can select between AUTO and MANUAL fan speed control.  

Pressing the FAN SPEED button, will switch speed from AUTO to MANUAL.  In MANUAL 
mode, pressing the FAN SPEED button will change fan speed from low to high.  In AUTO 
the fan speed is controlled automatically.  In cooling mode, the controller automatically 
adjusts the fan speed to high, and as the inside temperature approaches the set point, the 
fan speed will reduce.  In heat mode, the fan speed goes from low to high as the tempera-
ture approaches the set point 

 

 

TEMP SELECT—

Allows the operator to view the controller temperatures; INSIDE = re-

turn air temperature, OUTSIDE = supply air temperature, SET POINT can be seen and 
adjusted, by pressing ▲ or▼. 

CONTROLLER PROGRAMMING MENU 

 

1)  Make sure the unit has power. 
2)  Pushing the POWER button, turn the unit “OFF”. 
3)  Press the following buttons in sequence “S-U-D-S”:

 

4)  The display will begin flashing P1 and a number.

  

 
 
 
 
 
 

 

If there is no display, repeat the sequence, making sure the unit has power, but is turned 

OFF. 

 

5)  To adjust any program parameter, press the ARROW UP▲ or ARROW DOWN ▼ 
button until the desired value is displayed. 
6)  Use the “MODE” button to scroll through the programmable parameters P1 through 
P16. 
7)  If no buttons are pushed, the display will then return to the “OFF” position after about 
50 seconds. 

 

PROGRAMMING PARAMETERS 

 

P1—High Fan Speed Limit Setting 
P2—Low Fan Speed Limit Setting 
P4—Temperature Sensor Calibration 
P10— Temperature Display, °F or °C 
P13—Supply Fan Operation, Cycling or Continuous 
P15—Fan Motor Type Setting, PSC or Shaded Pole 
7) To cycle the evaporator fan with the compressor, access code P-

P1, P2 

- To adjust fan 

speed settings, P1 represents the high fan speed parameter, while P2 represents the low 
fan speed parameter.  When using nozzle kits, discharge duct adapters and evaporator 
plenums, setting P1 to 85 will help to avoid freeze ups.   

 

P4

 - Adjust the P4 setting to match the actual INSIDE room temperature, if needed. 

 

P10

 - Use this parameter to display temperatures in the desired units. 

 

P13

 - To cycle the evaporator fan with the compressor, access code P-13. Press the up 

or down button to switch to “CYC”, which means cycle the fan with the compressor. The 
factory default setting is “CON”, which means continuous fan operation. 

 

P15

 - Fan Motors are PSC type, SC - should be selected.

 

 

 

8)  Press POWER—you should see a code A (followed by numbers) 

 

Press POWER and the unit will start at the new settings 

Summary of Contents for OWC series

Page 1: ...ENGINEERING INSTALLATION AND SERVICE MANUAL OWC series Deluxe Portable Water Cooled Spot Cooler Form EISM OWC 110114 Rev 1...

Page 2: ...nd operation of the Oceanaire Air Boss spot cooler It is recom mended to read and fully understand the instructions outlined within this manual before operating the AQUACOOLER unit As with all commerc...

Page 3: ...bjects through a dis charge grill located on the upper front of the unit while rejecting heat from the top of the unit The AQUACOOLER models range in cool ing capacities from 12 000 BTU HR to 60 050 B...

Page 4: ...2...

Page 5: ...ndensate tank is full and needs to be emptied In the 5 ton AQUACOOLER units model OWC60 CON indicates a condensate pump over flow condition where the pump is either disabled or incapable of rejecting...

Page 6: ...ACOOLER is it operates as a room air conditioner because water is used as the means for heat rejection The major convenience of water cooled air conditioning is the convenience of connecting water hos...

Page 7: ...lity Re fer to the chart below for plug and receptacle details for all AQUACOOLER models A DAMAGED LCDI POWER SUPPLY CORD MUST BE REPLACED WITH A NEW POWER SUPPLY CORD OBTAINED FROM OCEAN AIRE AND NOT...

Page 8: ...ED IT IS RATED AT LEAST 20 AMPS 250 VOLTS 3 PHASE FOR MODELS OWC6032 AN EXTENSION CORD MAY BEUSED PRO VIDED IT IS RATED AT LEAST 30 AMPS 250 VOLTS 3 PHASE FOR MODELS OWC3634 AND OWC6034 AN EXTENSION C...

Page 9: ...7 AQUACOOLER UNIT ACCESSORIES...

Page 10: ...M DEP 10 10 Inch Round OWC12 DEP 12 12 Inch Round OWC18 24 36 DEP 16 16 Inch Round OWC60 DISCHARGE DUCT ADAPTER DDA 6 6 Inch Round OWC12 DDA 10 10 Inch Round OWC18 24 2DDA 16 16 inch Round OWC36 DDA 1...

Page 11: ...ximate extended length is 21 inches NK 2 for models OWC18 and OWC24 with 2 6 inch diameter nozzles with an approximate compressed length of 22 inches The approximate extended length is 32 nches 2NK 3...

Page 12: ...configuration and application information DEP 10 for OWC12 transitions the return air opening to a 10 inch round duct DEP 12 for OWC18 and OWC24 transitions the return opening to a 12 inch round duct...

Page 13: ...verts the evaporator discharge to a 10 inch diameter round duct 2DDA 16 for OWC36 converts the evaporator discharge to a 16 inch round duct DDA 16 FOR OWC60 converts the evaporator discharge to a 16 i...

Page 14: ...ose kits have FEMALE flare connectors to match the MALE flare fittings on the units see chart below The WATER IN connector consists of a 3 4 hose barb WATER OUT and DRAIN condensate have no fitting an...

Page 15: ...ssure are avail able CUPRO NICKEL CONDENSER When chemically treated water salt water or brine is used in the conden ser coil it is recommended that the AQUACOOLER be equipped with a 90 10 Cupro Nickel...

Page 16: ...cated on the back of the unit to make certain that the proper power is available for the unit Refer to Specifications section for voltage and amperage requirements For proper NEMA receptacles refer to...

Page 17: ...will then go blank Press the POWER button then press the TEMP SELECT button until the SET POINT is displayed Adjust the SET POINT to the desired temperature and the unit will heat cool as required Th...

Page 18: ...d value is displayed 6 Use the MODE button to scroll through the programmable parameters P1 through P16 7 If no buttons are pushed the display will then return to the OFF position after about 50 secon...

Page 19: ...urs 03 and 486 3486 hours 01 and 59 1059 hours TOTAL HOURS REPRESENTS COMPRESSOR RUN TIME MODEL CODE SETTINGS OWC12 P1 85 P2 35 OWC18 P1 80 P2 50 OWC24 P1 70 P2 50 OWC36 P1 85 P2 40 OWC60 P1 85 P2 45...

Page 20: ...he water supply line In these cases it is recommended that the water valve be adjusted 1 Disconnect the unit power 2 Remove the unit back panel and locate the water regulat ing valve in the lower righ...

Page 21: ...to locate the control box Disconnect wires and remove power module Install new power module and re wire in accordance with the wiring diagram C CONDENSATE PUMP ALL UNITS 1 Remove back panel and left...

Page 22: ...MEDY Make sure set point is lower than room temperature Look for a red dot to the right of the temperature displayed for cooling Note there is a delay for the compressor CAUSE Thermostat Loose display...

Page 23: ...hem in a solution of warm water and detergent for 10 minutes Then rinsing them clean with hot water and shaking excess moisture from filter CONDENSATE PUMP Condensate pumps come standard on all AQUACO...

Page 24: ...22...

Page 25: ...23...

Page 26: ...24...

Page 27: ...25...

Page 28: ...26...

Page 29: ...27...

Page 30: ...28...

Page 31: ...29...

Page 32: ...accordance with the furnished written instructions or has been altered or modified in any way b to any expenses including labor or material incurred during removal or reinstallation of the Product c t...

Reviews: