34 of 59
AC Instance 5 – Sixth AC Instance
Hex Addr
Dec
Addr
Data Field
Data Type, Range and Resolution
0x00C4
0196
AC Type
Unsigned 16 bit integer
Range 0 – 2, 0 = Bus, 1 = Utility, 2 = Generator
Resolution 1
0x00C5
0197
Average Line to Line
Voltage, AC, RMS
Unsigned 16 bit integer
Range 0 – 64255 Volts
Resolution 1 Volt
0x00C6
0198
Average Line to Neutral
Voltage
Unsigned 16 bit Integer
Range 0-64255 Volts
Resolution 1 Volt
0x00C7
0199
Frequency
Unsigned 16 bit integer
Range 0 – 501.99 Hertz
Resolution 1/128 Hertz
0x00C8
0200
Current
(Not available in Bus Type)
Unsigned 16 bit integer
Range 0 – 64255 Amps
Resolution 1 Amp
Memory addresses from 0x00C9 (0201) to 0X015E (350) reserved
7.14
AC Instance 5 Registers