16
www.ochsner.com | 00_200_202_03_01_002_AIR85-EN
Machine-specific engineering and preparation
8.
Machine-specific engineering
and preparation
Material damage
Air pressure and air humidity will affect the opera
-
tional reliability of the electrical components in the
heat pump system (dielectric strength).
»
Observe the maximum installation altitude of
the heat pump system.
Unit
Max. installation altitude (above
sea level)
AIR 85
m
1000
8.1 Outdoor unit
8.1.1 Installation location
►
The outdoor unit must not be surrounded by walls/
objects on all four sides.
►
The outdoor unit must not be surrounded by walls/
objects on three sides.
►
The outdoor unit must not be positioned immediately
adjacent to walls/objects on two sides.
►
The outdoor unit may be positioned adjacent to walls/
objects on two sides, provided the machine-specific
minimum clearances are observed.
►
It is permissible to install the outdoor unit under a roof
if the unit is permanently surrounded by open space
on three sides and the machine-specific minimum
clearances are observed.
8.1.2 Minimum clearances
A
B
C
Minimum clearance
between outdoor
units
Unit
AIR 85
≥ 3 ≥ 1 ≥ 1
≥ 1
m