30
www.ochsner.com | PIA-982027-AIR 85-in-EN
Appliance installation
9.2.3 Connecting the appliance halves
»
Position both internal sides together without panel
covers.
»
Use screws to secure the appliance halves on both
sides. For this, use the 8 x M6 round head screws
provided and the self-locking nuts.
Information
The appliance halves must not be installed sepa-
rately from one another.
Information
The connecting pipes provided for the suction gas
and liquid lines are installed during commission-
ing by customer service or an authorised customer
service partner.
»
Set aside the connecting pipes and ensure
that no dirt gets into them.
Information
Rubber pads under the feet of the outdoor unit can
prevent damage and therefore corrosion. The rub-
ber pads are not included in scope of delivery.
»
If you use rubber pads, ensure that the
outdoor unit is aligned correctly during instal-
lation.
9.2.4 Positioning the appliance
»
Position the appliance on the prepared foundations.
»
Secure the legs of the outdoor unit on the foundations
using 4 fixing screws.
9.2.5 Dismantling the appliance casing
By removing the side appliance casing panels on the out-
door unit, you can gain access to the connection points
for the refrigerant lines and to the terminal boxes for the
electrical control and power supply cables.
»
Undo and remove the two fixing screws on the
underside.
»
Pull the side appliance casing panel down and away.
9.3 Connecting the heat sink system
WARNING: Burns
The water in the lines of the heat sink system may
be > 60°C. Touching the lines can result in burns.
»
Observe national and regional guidelines
when laying and insulating the lines.
Information
The hydraulic connection from the heat sink system
(WNA) to the heat pump may be made only by a
qualified contractor.
Information
For maintenance purposes, a shut-off valve should
be fitted to every hydraulic line close to the connec
-
tion point on the heat pump.
Summary of Contents for 288800V
Page 2: ......
Page 7: ...PIA 982027 AIR 85 sh EN www ochsner com 7 ...
Page 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work ...
Page 45: ...PIA 982027 AIR 85 td EN www ochsner com 45 System principle schematic ...
Page 53: ...PIA 982027 AIR 85 EN01 www ochsner com 53 ...
Page 54: ...Notes ...
Page 55: ...Notes ...