PIA-982027-AIR 85-td-EN | www.ochsner.com 41
Data table
Control circuit
AIR 85 C14A
Rated voltage range
V
~220-240
L1/N/PE
Rated current
A
6,3
Fuse protection
1x C13A 1p
HEAT SINK SYSTEM
AIR 85 C14A
Heat transfer medium
Water
Max. heat transfer medium op. pressure
bar
10
Temperature differential (WNA)
K
5
Flow rate (WNA)
m³/h
10,9
Residual head (WNA)
mbar
818
Flow meter
FM 50 x 2” fem. kvs 40
external
3-way switching module (DHW)
DN50 (2”), kvs 40
external
Circulation pump
Stratos Para 65/1-12
external
Condenser type (WNA)
Plate heat exchanger
Condenser material (WNA)
Stainless steel 1.4301
PERFORMANCE FIGURES
Weight (excl. packaging)
kg
295
A7/W35
AIR 85 C14A
Heating output (EN14511)
kW
68,10
Power consumption (EN14511)
kW
13,97
Coefficient of performance COP (EN14511)
4,87
A2/W35
AIR 85 C14A
Heating output (EN14511)
kW
50,17
Power consumption (EN14511)
kW
12,95
Coefficient of performance COP (EN14511)
3,87
A-7/W35
AIR 85 C14A
Heating output (EN14511)
kW
47,90
Power consumption (EN14511)
kW
13,32
Coefficient of performance COP (EN14511)
3,60
A2/W55
AIR 85 C14A
Heating output (EN14825)
kW
51,92
Power consumption (EN14825)
kW
18,80
Coefficient of performance COP (EN14825)
2,76
A35/W7
AIR 85 C14A
Cooling capacity (EN14825)
kW
38,80
Power consumption (EN14825)
kW
15,50
Energy efficiency ratio EER (EN14825)
2,50
ENERGY EFFICIENCY (AVERAGE CLI-
MATE ZONE)
AIR 85 C14A
at max. flow temperature (heating)
°C
35
55
Energy efficiency class (D to A+++)
A++
A++
P rated
kW
54
56
Efficiency ETAs
%
169,6
136,7
SCOP
4,32
3,49
at min. flow temperature (cooling)
°C
18
7
SEER
3,6
3,26
Summary of Contents for 288800V
Page 2: ......
Page 7: ...PIA 982027 AIR 85 sh EN www ochsner com 7 ...
Page 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work ...
Page 45: ...PIA 982027 AIR 85 td EN www ochsner com 45 System principle schematic ...
Page 53: ...PIA 982027 AIR 85 EN01 www ochsner com 53 ...
Page 54: ...Notes ...
Page 55: ...Notes ...