8
www.ochsner.com | 00_400_200_202_01_split_Funktionsweise-EN
How split systems work
3. How split systems work
An air/water heat pump extracts thermal energy from the
ambient air (low temperature) and transmits it together with
electrical drive energy in the form of useful heat (higher
temperature) to a heating and/or DHW circuit.
The heat pump consists of separated circuits linked togeth-
er via heat exchangers:
►
Heat source circuit (extracting heat)
►
Refrigerant circuit
►
Heat sink circuit (supply of heat for room heating and/
or DHW)
Outdoor air is a heat source that is available everywhere
in unlimited amounts and can be utilised without approval.
It is especially suitable for retrofitting.
A split system consists of an indoor unit and a separately
installed outdoor unit. The outdoor air is routed through the
outdoor unit by means of a fan. The indoor and outdoor
units are connected through refrigerant lines.
Due to the defrosting mode integrated into OCHSNER air/
water heat pumps, the system also operates flawlessly at
temperatures below -15°C.
For air/water heat pumps, the most efficient and therefore
most common operating mode is bivalent parallel opera-
tion.
Due to the integral defrosting mode, the monovalent op-
erating mode is also possible. As the heating output of an
air/water heat pump at an outdoor temperature of +15°C
is approx. triple the heating output at -15°C, such systems
are vastly oversized for operation in spring and autumn
and therefore not recommended.
1 Evaporator (outdoor unit)
2 Compressor
3 Condenser (plate heat exchanger)
4 Expansion valve
5 Heat sink (heating, DHW)
Summary of Contents for 288800V
Page 2: ......
Page 7: ...PIA 982027 AIR 85 sh EN www ochsner com 7 ...
Page 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work ...
Page 45: ...PIA 982027 AIR 85 td EN www ochsner com 45 System principle schematic ...
Page 53: ...PIA 982027 AIR 85 EN01 www ochsner com 53 ...
Page 54: ...Notes ...
Page 55: ...Notes ...