3
3.4.1.2.6.Set the target gateway address that you want to download.
And it could set the download communication port number through
“Communication”→“Configure communication channel” too. The gateway factory
default IP is 192.168.1.254 and port number is 1024.
3.4.1.2.7.Click the button “Download Gateway Configuration ” to.
download configuration parameters to the gateway.
After the download is successful, the "Download successful" prompt appears in
the Status Bar at the lower right. After the download is successful, the gateway restarts
automatically and then the it goes into running state.
If the download fails, please check out whether the computer IP address and
gateway IP address are in the same network segment. Then check whether the gateway
IP address is set correctly. If the gateway IP address is lost, please reset the gateway
through the reset button. After reset, the gateway IP address will be the factory default
IP address.
Click "Import Profile" and "Export Profile" and it could import or save the
configuration file to the local disk. Click “Upload Gateway Configuration” and it could
upload the current gateway configuration to the software.