3. OPERATING PRINCIPLE 

To the paddle(1), which is soaked in the fluid, through a rod, a 
small piston (2) made from magnetic stainless steel is 
connected; this small piston is housed in a pit (3) made from 
non-magnetic material. 
On the pit (3) a tripping device, which is drawn schematically 
beside, is mounted. It is composed of a magnet (4) and a 
miniature switch (5) that are connected to one another by 
means of levers. 
In low flow-rate conditions (fig.“A”), the magnet (4) is at rest, 
whereas in high flow-rate conditions (fig.“B”), the magnet (4) 
is attracted by the small piston (2) that causes the miniature 
switch (5) to operate. 
The difference between high and low flow-rate is called 
”tripping differential”. 
The arrow indicates the direction fo the flow. 

 
 
4. INSTALLATION 

4.1 INSTALLATION ON THE SYSTEM  

 

Before installation, check the line connections for compatibility with the instrument connections. 
The flow switch shall be installed in a perfectly upright position and the piping shall be straightaway for at least 5D 
upstream and 3D downstream. 
The flow switch body has an arrow indicating the direction 
taken by the flow; comply with such indication at the assembling 
stage. 
Remove the adhesive tape that locks the paddle and the plastic 
strip inserted in the tube, so that the stem becomes free to move. 
Ensure that the entire paddle is inside the piping and that, at rest 
(no fluid), it does not touch the bottom of the piping. 
It is strictly prohibited to load the instrument with external loads 
and it is the user’s duty to protect it from strain; do not use it as 
resting point. 
To avoid effects of galvanic corrosion, any use of materials 
featuring a different electrochemical potential is prohibited. The 
user shall adopt all those technical devices that can prevent this 
event from occurring. 
The system shall be equipped with the specified technical 
device, to make up for overpressure going beyond the 
maximum envisaged point. 
For installation on piping exposed to strong vibration, 
please contact the Customer service department. 

 
 

4.2 WIRING 
The  flow  switch  has  a  terminal  board  inside  the  case  for  NC  -  C  -  NO  connections (see 
figure on the right). 
Make sure that the cover of the housing is closed properly before powering up. 
The user shall provide suitable ground connections that are such as to protect the staff and 
any other equipment possibly present. 
The NC-NO condition referred to herein is with null fluid.

  

 
 

NO  =NORMALLY OPEN 
C =  COMMON  
NC  =NORMALLY CLOSED

 

 
 

Summary of Contents for PL Series

Page 1: ...right position along horizontal pipes These models are equipped with a tripping device which can be equipped with single SPDT or double DPDT exchange contacts for high or low flow rate control and or...

Page 2: ...stream and 3D downstream The flow switch body has an arrow indicating the direction taken by the flow comply with such indication at the assembling stage Remove the adhesive tape that locks the paddle...

Page 3: ...replace any components without having first read the relevant instructions carefully If in doubt contact our Customer Services NEVER lubrificate instrument components If being used with high temperat...

Page 4: ...s to the terminal board as per point b 7 6 SETTING THE OPERATION POINT The switching unit is factoryt set to the minimum operation value To set the operation point to the desired flow rate value take...

Page 5: ...biche it JULY 14 Information subject to change without prior notice IST 158 I 9 DRAWINGS OF CASE WITH DIMENSIONS CODE LIQUID TEMPERATURE ELECTRICAL CONNECTIONS A 10 135 EP WP R3 11 80 1 2 NPT 1 2 NPT...

Page 6: ...e mail info officineorobiche it JULY 14 Information subject to change without prior notice IST 158 I WP CASE WATER PROOF IP 66 10 RECOMMENDED SPARE PARTS When ordering spare parts always indicate the...

Page 7: ...the improper use of the instrument Officine Orobiche may not be held liable for any improper use of its products where these are used for ends other than those indicated in the specifications forming...

Reviews: