43
Parameter
Scale
Low
Scale
High
Notes
61
62
63
64, 128
65, 129
68
69
70
71, 140
72
73
74
75
76
77
78
79
66
130
67
131
BPL1
BPL2
CJCL
PV
SV
TIMER
EROR
MODE
PROG
CMND
JOB1
JOB2
JOB3
MV1
MV2
Bumpless transfer of OP1
Bumpless transfer of OP2
Cold junction signal low
Process value
Current set point value
Remaining time of dwell timer
Error code *1
Operation mode & alarm status *2
Program code *3
Command code
Job code
Job code
Job code
Cold Junction Temperature
Reserved
Reserved
Reserved
OP1 control output value
OP2 control output value
0.00
0.00
0.000
*4
*4
-1999.9
0
0
0.00
0
0
0
0
-199.99
0
0
0
0.00
0.00
655.35
655.35
65.535
*4
*4
4553.6
65535
65535
655.35
65535
65535
65535
65535
455.36
65535
65535
65535
655.35
655.35
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
Register
Address
Parameter
Notation
Read only,
unless in
manual
control
Read only,
unless in
manual
control
*1: The error code is show in the first column of Table A.1.
*2: Definition for the value of MODE register
H'000X = Normal mode
H'010X = Calibration mode
H'020X = Auto-tuning mode
H'030X = Manual control mode
H'040X = Failure mode
H'0X00 = Alarm status is off
H'0x01 = Alarm status is on
The alarm status is shown in
MV2 instead of MODE for
models C21 and C91.
CJCT