5000 Series Indicators
Contact
Set the tmng of the relay contacts.
SIM = relays open or close at the same tme.
b-b-M = relay opens before the next relay closes (break before make).
M-b-b = relay closes before the next relay opens (make before break).
NOTE
: A 100 ms delay or over-lap s used for the break-before-make and make-before-break tmng.
Stable
Set how the relay outputs react durng nstablty.
OFF = relay changes are mmedate.
ON = delays relay changes untl weght readng s stable.
.11.5 End I-O
Advance to the next menu.
.1 Menu Lock Menu
Reset
No
, Yes
Lock Calbraton Menu
Off
, On
Lock Setup Menu
Off
, On
Lock Readout Menu
Off
, On
Lock Mode Menu
Off
, On
Lock Unt Menu
Off
, On
Lock Prnt1 Menu
Off
, On
Lock Prnt2 Menu
Off
, On
Lock Com1 Menu
Off
, On
Lock Com2 Menu
Off
, On
Lock GMP Menu
Off
, On
Lock I-O Menu
Off
, On
End Lock Menu
Use ths menu to prevent unauthorzed changes to menu settngs. When the securty
swtch s set to ON, the locked menus can be vewed but not changed. Default settngs
are
bold
.
.1.1 Reset
Set the menu Lock menu to factory defaults.
NO = not reset.
YES = reset.
NOTE
: Settngs for LFT controlled menu tems are not reset.
.1. Lock Calibration
Set the status.
OFF = Calbraton menu s not locked.
ON = Calbraton menu settngs s locked.