MODEL / RATED OUTPUT (kW)
3~ 400 V, 50 Hz, PE
WATER AND ETHANOL
SOLUTION, 30 m-% OF ETHANOL
6
8
10
13
17
21
CUBE
m 1.7
2.0
2.5
3.0
-
-
Pump head for external pressure loss
ECO
m 6.1
5.1
5.6
3.5
9.8
8.0
CUBE
m 5.9
4.8
5.0
2.7
-
-
Brine 0 °C / –4 °C and water 30 °C / 35 °C (B0/W35)
Brine temperature difference
°C 4
4
4
4
4
4
Brine flow rate (total)
kg/s 0.26 0.35 0.48 0.61 0.81 1.02
Brine flow rate (total)
L/s 0.27 0.36 0.50 0.63 0.84 1.05
Brine flow rate (total)
m3/h 0.98 1.31 1.79 2.27 3.02 3.78
Pump head, standard pump
m 7.6
7.6
8.2
7.4
11.8 11.9
Pump head for pumps delivered on special order
m 9.2
9.3
11.4 11.7
Internal pressure loss
ECO
kPa 9
10
11
20
12
17
CUBE
kPa 10
12
15
17
Internal pressure loss expressed in terms of pump
head
ECO
m 1.0
1.1
1.2
2.2
1.3
1.8
CUBE
m 1.1
1.2
1.5
1.8
-
-
Pump head for external pressure loss
ECO
m 6.6
6.5
7.0
5.2
10.5 10.1
CUBE
m 6.5
6.4
6.7
5.6
-
-
6.6 Pumps
Pumps
Oilon
designation:
Pump
Information
A 34023071
Wilo-Yonos PARA GT
15/7.5 PWM1 130 mm 6h
1-phase, wet-motor, G 1 outer thread,
installation dimension 130 mm, inverse PWM, 4–
75 W (0.04–0.66 A)
B 34023129
Grundfos UPMXL
GEO 25-125 180 PWM
1-phase, wet-motor, G 1 1/2 outer thread,
installation dimension 180 mm, inverse PWM, 3–
180 W (0.04–1.42 A)
C 34023075
Wilo-Stratos PARA
25/1-12 T16 180 mm 6h
1–phase, wet-motor, G 1 1/2 outer thread,
installation dimension 180 mm, manual control
and 0–10 V, 16–310 W (0.16–1.37 A), motor
protection 1.6–2.5
48 (54)
M8006 2123EN