2.7 O
2
module technical data (WD200)
O
2
module
PLL52...
Mains voltage, sensor heating
110 VAC –15/+10 %
Mains voltage
2 x 12 VAC
Power consumption
4 VA
Analog inlet, oxygen sensor
QGO20.000D27
Analog inlet, combustion temperature
Pt1000 / LG-Ni 1000
Analog inlet, flue gas temperature
Pt1000 / LG-Ni 1000
Analog inlet, bus interface
CAN
Protection degree
NEMA 3
Permissible ambient temperature
-20...+60 °C
-4..+140 °F
Protect the equipment from condensation, ice and water ingress.
2.8 Oxygen sensor technical data (WD200)
Oxygen sensor
QGO20...
Measuring cell
ceramic zirconium dioxide cell
Mains voltage, measuring cell heating
110 VAC –15/+10 %
Power consumption
max. 90 W, typically 35 W
Measuring cell temperature
700 °C ±50 °C
1292 °F ±122 °F
Measuring range
0.2…20.9 % O2
Flue gas velocity
1…10 m/s
3.28...32.81 ft/s
Protection degree
NEMA 2
Max. temperature, flange
+250 °C
+482 °F
Max. temperature, connecting head
+70 °C
+158 °F
Max. temperature, flue gas
+300 °C
+572 °F
Protect the equipment from condensation, ice and water ingress.
18 (129)
M5178 1647EN
Summary of Contents for GKP-350 M
Page 2: ......
Page 5: ...6 15 Burner part list 129 M5178 1647EN 3 129...
Page 6: ...4 129 M5178 1647EN...
Page 18: ...Block diagram of contact links Block diagram ver 5 16 129 M5178 1647EN...
Page 100: ...5 5 Time sequence diagram gas use Time sequence diagram G ver 3 98 129 M5178 1647EN...
Page 101: ...Time sequence diagram Gp1 ver 5 M5178 1647EN 99 129...
Page 132: ...130 129 M5178 1647EN...
Page 133: ......