To adjust outlet pressure
219598a ver. 1
1. Unscrew protective cap
A
.
2. Use a chisel-point screwdriver. to adjust spindle
B
:
a. Turn the spindle B clockwise. This increases the outlet pressure.
b. Turn the spindle B counterclockwise. This reduces the outlet pressure.
3. Check the setpoint.
4. Screw on the protective cap
A
.
To replace setting spring
219598b ver. 1
1. Remove protective cap
A
. Release spring by turning adjustment spindle
B
counterclockwise. Turn spindle to stop.
2. Unscrew complete adjustment spindle
B
and remove spring
C
.
3. Insert new spring
D
.
4. Assemble complete adjustment spindle and adjust desired offset.
5. Screw on protective cap
A
. Stick adhesive label
E
onto typeplate.
Excessive tightening of screws may damage the component.
Sealing final settings
1. Check pressure regulator outlet pressure. If necessary, adjust it to be sufficient for
full load setting.
2. Finally seal setting by threading wire through sealing holes in protecting cap and
pressure regulator body.
54 (129)
M5178 1647EN