Point22 ver. 3
4. Display the changes. The third line shows the current residual oxygen level. The
pointer is on
StandardVal
. Reduce the air by pressing the
Select -/+
buttons, if
necessary. Larger level at this point, means larger air throttle. When desired oxygen
level is reached, press
Enter
.
Point23 ver. 3
5. Display the changes.
Save or reject by pressing
Enter
.
Point24 ver. 3
At curve point 2, and at the highest curve point, the burner control calculates PI
parameters, and time delays for O
2
monitor by driving the burner back to ratio
curve. After that the display returns to initial state.
Select next curve points from the menu by pressing the
Select -/+
buttons, and
set O
2
setpoints from them. If flue gas speed in ratio curve point 2 is too low, O
2
monitoring set value calculation does not succeed. The burner control notifies this in
the operating and display unit.
O
2
monitoring first point can be set later using the parameter
Adapt.Pointsmall
.
Point25 ver. 3
M5178 1647EN
77 (129)