SW_FilterTimeCon. can be used to delay the internal load controller. If the value for this
parameter is too high, the internal load controller becomes unstable. The factory setting
is 3s.
4.34 Capacity controller on/off
If temperature or pressure has been given a set value, burner start-up and shut
down limits are percentages of the set value. Calculate switching points according to
following example:
Setting
70 °C
158 °F
Mod_On
Burner start
-10 % (=7 °C) 70 – 7 = 63 °C
-10 % (=44.6 °F) 158 – 44.6 = 113.4 °F
Mod_Off
Burner shutdown
+5 % (=3,5 °C) 70 + 3,5 = 73,5 °C
+5 % (=38.3 °F) 158 + 38.3 = 196.3 °F
Mod_On
is possible to set between
–50…+50 %
Mod_Off
is possible to set between
0…+50 %
Params. & Display
LoadController
ControllerParam
Mod_On
Mod_OFF
Example running period.
KAYNTIJAKSO ver. 2
4.35 Boiler temperature limiting with burner control
Boiler temperature can be limited with burner control. It can be implemented with the
same sensor used for temperature control, or with a separate sensor. When pressure
control is selected, temperature limiter is not in use.
If limiter temperature switch-on point is reached, burner shuts down. Burner restarts
when temperature limiter is reset.
Example:
M5178 1647EN
85 (129)
Summary of Contents for GKP-350 M
Page 2: ......
Page 5: ...6 15 Burner part list 129 M5178 1647EN 3 129...
Page 6: ...4 129 M5178 1647EN...
Page 18: ...Block diagram of contact links Block diagram ver 5 16 129 M5178 1647EN...
Page 100: ...5 5 Time sequence diagram gas use Time sequence diagram G ver 3 98 129 M5178 1647EN...
Page 101: ...Time sequence diagram Gp1 ver 5 M5178 1647EN 99 129...
Page 132: ...130 129 M5178 1647EN...
Page 133: ......