4.14 Manual start-up and program stop in pre-purge position
Program stop
With burner control
ProgramStop
parameter burner start-up can be stopped in
selected program phase, and servomotor position can be adjusted.
Pre-purge position
phase 24–34
Ignition position
phase 36
Transition 1
phase 44
Transition 2
phase 52
Post-purge
phase 72–78
Active program stop in phase 24.
Params & Display
Ratio Control
Program Stop
deactivate
24 PrePurgP
32 PreP FGR
36 IgnitPos
44 Interv 1
52 Interv 2
72 PostPPos
76 PostPFGR
Manual start-up
Prerequisites:
● Frequency converter parameters are set and adjusted.
● Interlocking and failures are reset.
● Program phase is 12,
Stand by
.
● In heavy fuel oil use preheater temperature is sufficient.
Activate manual burner start-up from menu level
Autom/Manual/Off
by choosing
BurnerOn
:
ManualOperation
Autom/Manual/Off
Auto
BurnerOn
BurnerOff