1. If the set value does not reach the set step within the maximum time, the load will
be increased by one stage step.
2. If the set value has reached the set step before the maximum time has elapsed, the
load increases by one stage step.
The menu shows values used in the chart example.
Example,
Set value 145 PSI
Params. & Display
LoadController
ColdStart
ColdStartOn
activated
ThresholdOn
40% of set value
StageLoad
15% load step
StageSetp_Mod
10% of set value
StageSetp_Stage
MaxTmeMod
5 minutes
MaxTmeStage
ThresholdOff
80% of set value
AdditionalSens
Setp AddSensor
Release Stages
Cold start thermal protection operation example.
Cold start ver. 4
72 (102)
M4263 2206EN