● gas inlet pressure is correct
● equipment is installed correctly and is in working condition
● chimney is properly connected, unobstructed and flue gas damper is open
To start the burner:
1. Open the manual fuel shut-off valves.
2. Switch on power supply.
3. Switch on the burner from the burner control switch.
To stop the burner:
Turn the burner control switch to OFF position.
Commissioning data
● Gas type
● Wobbe index (calorific value)
● Volumetric gas flow rate
● Minimum and maximum heat output rates
● Supply gas pressure
● Adjusted gas pressure
● CO and CO2-percentage content of the flue gases
● O2- percentage content of the flue gases
● Combustion air temperature
● Flue gas temperature
● Gas nozzle pressure
● Fan pressure
● Air and fuel servomotor positions