Curve point 2 ver. 4
The pointer is positioned at the colon below the text
Point
. The running number of the
stored curve point is shown after the colon.
Curve points are stored according to capacity from smallest to biggest. Curve points
can be added at any order. Scroll through curve points using the
Select -/+
buttons.
The setting for an unused curve point is
XXXX
and its running number is one number
greater than that of the last stored curve point.
If you want to set a new curve point, press
Enter
, when
XXXX
is displayed as the set
value.
The ignition position will automatically be set as the first ratio curve point, from which
the burner minimum load point is adapted.
Editing individual curve point
To change an existing curve point:
1. Select the desired point and press
Enter
.
2. The pointer is positioned on
change?
below
Point
. The running number of the
curve point to be changed is displayed after the colon.
Curve point 3 ver. 4
3. Select the desired value using the
Select -/+
buttons, and press
Enter
.
●
change
changes the curve point settings
●
delete
deletes the curve point
Pointer positioned at
Load
.
Curve point 4 ver. 4
M4248 2316EN