Inputs / outputs (VSD)
Connection diagram ver. 3
2.4 Servomotor technical data
Servomotor
SQM45...
SQM48.497
SQM48.697
SQM91.391A9
Mains voltage
2 x 12 VAC
2 x 12 VAC
2 x 12 VAC
2 x 12 VAC
Power consumption
9 – 15 VA
26 – 34 VA
26 – 34 VA
40 VA
Angular adjustment
90°
90°
90°
90°
Accuracy
±0.2°
±0.2°
±0.2°
±0.8°
Torques, operation /
holding
26.55 / 13.27 lbf·in
177 / 177 lbf·in
310 / 310 lbf·in
531 / 531 lbf·in
Running time
10 s - 120 s
30 s - 120 s
60 s - 120 s
30s
Degree of protection
NEMA 3
NEMA 3
NEMA 3
NEMA 4
Permissible ambient
temperature
-4...+140 °F
-4...+140 °F
-4...+140 °F
-4...+140 °F
2.5 Display and operating unit technical data
Display and operating unit
AZL...
Supply voltage
24 VDC –15/+10 %
Power consumption
< 5 W
Protection degree
NEMA 3
Permissible operation ambient temperature
-4...+140 °F
Protect the equipment from condensation, ice, and water ingress.
2.6 O
2
module technical data (WD200)
O
2
module
PLL52...
Mains voltage, sensor heating
110 VAC –15/+10 %
Mains voltage
2 x 12 VAC
Power consumption
4 VA