Combustion air US ver. 1
Guideline values
Capacity
Fuel
O2 level %
Ignition, minimum and part capacity
Gas
3.5–4.5
Full capacity
Gas
2–4
If you alter the position of the adjustment ring in relation to the diffuser
disc, the quantity and velocity of combustion air in the combustion head
will change. Check combustion values with flue gas analysis and, if
necessary, adjust combustion air quantity to an adequate level.