Manual start-up
Prerequisites:
● Frequency converter parameters are set and adjusted.
● Interlocking and failures are reset.
● Program phase is 12,
Stand by
.
● In heavy fuel oil use preheater temperature is sufficient.
Activate manual burner start-up from menu level
Autom/Manual/Off
by choosing
BurnerOn
:
ManualOperation
Autom/Manual/Off
Auto
BurnerOn
BurnerOff
Gas use
Primary safety control
Prepurge: four air changes in max. 90 s. (Burners not exceeding 2,500 MBtu/h)
Prepurge: 30 s at maximum air damper opening (high fire).
If a curve point setting for full load is changed, adapt the changes to the
pre-purge position settings.
After the pre-purge stage, the air in the combustion chamber must be
completely fresh.
If servomotor AUX3 is in use and
ProgramStop
is moved to phase 32,
the servomotor will not change position until phase 32.
4.14 Ignition position
Set program stop at phase 36,
ignition
.
Burner control carries out automatic gas valve leak test during pre-purge, if:
52 (111)
M4219 2305EN
Summary of Contents for GP-600 M
Page 2: ......