Working diagrams
Using the burner outside the range shown in the working diagrams is
not allowed.
‘’W
.C
.
GP-600 M - 700 M-III (UL) ver. 1
Tested in laboratory conditions (ambient temperature 68 °F).
2.2 Other technical data and requirements
Fuel, gas use
Natural gas
When using other gases than natural gas, the composition
of the gas must be known. Consult burner manufacturer on
the suitability of the burner for special gases.
Gas inlet pressure to burner max.
Natural gas:
8 - 200 "W.C.
LPG:
11 - 200 "W.C.
Max. demand for combustion air, gas use
13.5 cfh/MBtu
Efficiency, natural gas
35,31 ft³n/h ≈ 13.5 MBtu efficiency, when heat value is
961.91 Btu/ft³
Performance, natural gas
950 - 1050 btu/sc.ft
Control voltage
115 V (-15%...+10%) 50 Hz / 60 Hz 1-phase
Motor voltage options
220 V 60 Hz 3-phase
400 V 60 Hz 3-phase
460 V 60 Hz 3-phase
575 V 60 Hz 3-phase