1
Temperature sensor
4
Butterfly valve
2
FGR pipe (*)
5
Burner
3
Sleeve (*)
A
Min. 7.87 in
* not included in delivery
3.10 Changing the fuel type from natural gas to LPG
This information applies only when liquefied petroleum gas (LPG) is
used.
Gas nozzle adjusting band (LPG) ver. 3
1
Adjusting band
2
Gas nozzle
3
Fixing screw of adjusting
band
To use the burner with liquefied petroleum gas (LPG), install an adjusting band in the
gas nozzle, allowing you to adjust the square area of the nozzle apertures.
● Adjust the final position of the band according to the capacity demand.
● Note the quantity of gas flow in relation to function of the compound regulator.
● Check the combustion values with flue gas analysis and, if necessary, adjust the
burner by changing the air damper and the gas pressure.
● After the conversion, supplement the burner’s type plate with a label or other
marking indicating the type of gas fired in the burner.
3.11 Electrical connections
Electrical installation may be carried out by authorized and trained
personnel only.
Connect the burner according to the electrical diagrams delivered with burner. Follow
general and local standards and regulations as well as requirements set for electrical
connections for electrical equipment.
M4219 2305EN
29 (111)