● gas inlet pressure is correct
● equipment is installed correctly and is in working condition
● chimney is properly connected, unobstructed and flue gas damper is open
To start the burner:
1. Open the manual fuel shut-off valves.
2. Switch on power supply.
3. Switch on the burner from the burner control switch.
To stop the burner:
Turn the burner control switch to OFF position.
Commissioning data
● Gas type
● Wobbe index (calorific value)
● Volumetric gas flow rate
● Minimum and maximum heat output rates
● Supply gas pressure
● Adjusted gas pressure
● CO and CO2-percentage content of the flue gases
● O2- percentage content of the flue gases
● Combustion air temperature
● Flue gas temperature
● Gas nozzle pressure
● Fan pressure
● Air and fuel servomotor positions
4.2 Adjusting combustion air
Adjustment ring positioning
Adjustment ring position has an effect on thif e pressure in the combustion head. Adjust
the pressure by moving the adjustment ring back and forth. This changes the gap
between the adjustment ring and the diffuser disc.
● At low capacity, the adjustment ring is at the front.
● At high capacity, the adjustment ring is at the back.
If...
Then...
Result
The adjustment ring is too
far forwards at full capacity
There is too much pressure
drop in the combustion
head.
● Poor ignition, OR
● Poor combustion due to inadequate amount
of air (high CO content), OR
● Flame tear-off from diffuser disc when
switching to higher capacity
The adjustment ring is too
far towards the back at low
capacity.
There is not enough
pressure drop in the
combustion head.
Poor combustion (O
2
values too high)
Minimum pressure drop in the combustion head
Fuel
"W.C
Gas use
0.8
32 (111)
M4219 2305EN
Summary of Contents for GP-600 M
Page 2: ......
Page 16: ...Block diagram of contact links Block diagram ver 7 14 111 M4219 2305EN...
Page 87: ...5 5 Time sequence diagram gas use 7550f57e 0515 Gp1 ver 6 M4219 2305EN 85 111...
Page 113: ...M4219 2305EN 111 111...
Page 114: ...112 111 M4219 2305EN...
Page 115: ......