Heat pumps in the cascade
M
S1
S2
Master
S0/G1
Line
6600 = 1
Slave
S0/G2
Line
6600 = 2
Slave
S0/G3
Line
6600 = 3
Master controller’s sensors, actuators, and
functions
S1 = Slave S0/G2
S2 = Slave S0/G3
6.2 LPB bus configuration
The system’s controllers are connected to an LPB bus (DB+/MB–). Any remote access
devices will also be connected to the same bus.
● Use twisted pair cables with a minimum wire cross-sectional area of 0.75 mm
2
.
Over long distances, use 1.5 mm
2
wires.
● Do not arrange the bus as a closed loop.
The permitted topologies are presented below.
Cascade bus topology ver. 1
The minimum voltage between the bus’s DB+ and MB– connectors is 9.5 V DC.
● If the voltage is smaller, the electrical resistance in the bus cables is too great.
M8009 2147EN
37 (74)