15. Use an oil flow meter to check minimum capacity. ( Minimum capacity preadjusted at
the factory )
16. increase capacity step-by-step by adjusting the screws.
17. Use a gas analyzer to adjust optimum values for the combustion.
18. Use an oil flow meter to check maximum capacity. ( Maximum capacity preadjusted
at the factory )
19. Test the safety equipments on the burner.
Never use a naked flame while checking the burner or the boiler. Never
store any inflammable material in the boiler room.
Wear hearing protectors, if there is noise in the boiler room.
4.2.
4.2.
Nozzle capacity charts
Nozzle capacity charts
4.2.1
4.2.1
Nozzle capacity charts Fluidics 12 W1
Nozzle capacity charts Fluidics 12 W1
Charts applicable when atomizing viscosity15 mm²/s (cSt)
34 (77)
RPMARINES 30820641GB
4. First start-up and adjusting