background image

© 2021 OJ Electronics A/S

33

Regulator (C):

 

 The thermostat functions as a simple regulator 
and no sensors are used. The setting is in per 
cent.  

”Regulator” mode in combination with 
”Night setback”

 

If both Regulator mode (APp 

a

 C) and ”Night 

setback” are selected, night setback is set in 
relative values while frost protection is set in 
absolute values in per cent.  
The setpoint specifies (in per cent) the time the 
unit is to remain active in a PWM cycle, which 
is usually 20 min, while setback degree is 
specified as a percentage of the setpoint.  
The setpoint multiplied by the setback degree 
gives the activation degree.  
 
Example: If the setpoint is set to 60 % and 
night setback is set to 25 %, the activation 
degree will be (0.60 x 0.25 = 0.15) = 15 %.

  Graphic 

example: 

 

Setpoint

nSb Setback

nSb Activation 

degree

Local 

Setpoint 

in APP “C” 

mode

The diagram should be read as follows:  
Furthest to the left is 100 % duration of PWM, 
while the vertical lines indicate successive  
20 % drops in the time heating is provided 
relative to 100 %. 

 

The black area indicates the percentage cut-
out time determined by the setpoint. 

 

Together with the light grey area, the dark grey 
area indicates the relative amount of operating 
time when nSb has not been activated, but the 
dark grey area cuts out when nSb is activated. 

 

The light grey area is the relative amount of 
operating time when nSb has been activated 
by the above-mentioned values. 

 

The default value of setback degree ”night 
setback” (nSb) is 30 %.

 

nSb is inactive as default. 

 

Frost protection ”dEF” has the specified acti-
vation degree and is unaffected by the setback 
degree in nSb.

Scale

Choose between degrees Celsius and a numerical scale. If the 
numerical scale is selected, temperature is set on a scale from 0.0 
to 10.0 where 0.0 corresponds to min. temperature (SCA 

a

Lo) and 

10.0 corresponds to max. temperature (SCA 

a

 Hi).

Temperature reading

Defines which temperature is to be shown on the start display: the 
setpoint (SP) or the actual, measured temperature. 

Adjust offset

If the actual temperature (measured using a thermometer) differs 
from that displayed by the thermostat, the thermostat can be 
adjusted to offset the difference.

Control method

PWM or ON/OFF control can be selected. PWM is an advanced 
control method which calculates the most effective and economi-
cal way to heat homes and other buildings. ON/OFF control is 
traditional differential control (e.g. 0.3 °C) for other tasks. 

PWM cycle time 

Allows cycle time to be set when using PWM control. At least 20 
min is recommended. 

ETN4-1999  

 English

Differential temperature

Allows temperature differential to be set when using ON/OFF con-
trol. The higher the differential temperature, the lower the number 
of relay operations. 

Relay function

When used for heating purposes, the relay should be in normally 
open position (NO). If the thermostat is used for cooling purposes, 
the relay should be turned to normally closed (NC). 

EN50559

This thermostat complies with EN 50559 (VDE 0705-559) for 
electrical floor heating. The regulation applies to electrical floor 
heating, with a maximum floor weight of 4 kN/m². To ensure 
that hotspots due to unintentionally covering up the surface are 
avoided, the heating function can be time-limited as per EN/DIN.

Note that this function is not applicable to other heating applica-
tions such as wall and/or ceiling heating.
If it can be foreseen in advance that unintentional covering up of a 
floor might occur, then it is important to assess the correct period 
of time for which the floor heating must be time-limited.
The heating can be limited using a set number between 0 - 20 
minutes per hour. 

Example:
If obstacles could be present that cover up the floor, then the heat-
ing might need to be limited by some number of minutes so as to 
avoid hotspots in the floor. 
If you want the thermostat to heat a maximum of 90 % of the time, 
then the thermostat should be limited by 10 %. 
Ten percent of one hour is 6 minutes.
Enter 6 min. in the EN50559 menu in order to lower the heating by 
10 %.
Equation to calculate number of minutes that could be entered in 
the EN50559 menu - when an average heating effect is desired:

Average wanted heating effect pr. m

2

Floor heating element effect pr. m

2

(

1-

 

(

 )

)

 ∗ 

60 min.

Note! If the result of the equation is negative, then nothing should 
be entered.

Software version

Displays thermostat software version. 

 

TROUBLESHOOTING

Factory reset

Allows factory settings to be restored. Your personal settings will 
be deleted from the thermostat. 
Press and hold the centremost button for 10 seconds. The display 
is switched off and then on again. Application is shown on the 
display (APp 

a

F) followed by the temperature setting. 

Summary of Contents for ETN4-1999

Page 1: ...er button Programming ON OFF switch Left button Lower temperature Right button Raise temperature Heating ON Child lock or C Frost protection Temperature set point Night setback Thermostat The ON OFF b...

Page 2: ...n and max limits for floor temperature A floor sensor must be fitted Thermostat with sensor for APpa F Floor APpaA Room APpa Li Limit APpaAF Room floor limit APpa C Regulator Floor x x x Room x x Room...

Page 3: ...ced control method which calculates the most effective and economi cal way to heat homes and other buildings ON OFF control is traditional differential control e g 0 3 C for other tasks PWM cycle time...

Page 4: ...r defective or short circuited terminals 10 11 Replace sensor sensor cable To continue to operate the system without sensor set control type to Regulator under Application APp aC E2 External floor sen...

Page 5: ...r C Frostschutz Temperatur Sollwert Nachtabsenkung Thermostat Mit dem Ein Aus Schalter wird der Thermostat durch Kippen des Schalterknopfs aus 0 oder eingeschaltet I Bei ausgeschalte tem Thermostat 0...

Page 6: ...s anzuschlie en ist Raum Grenze AF Der Thermostat regelt die Raumtemperatur mit min und max Grenzen f r die Bodentemperatur Ein Bodenf hler muss montiert sein Thermostat mit Sensor f r APpaF Boden APp...

Page 7: ...nes Regelprinzip das sich auf die effizienteste und wirt schaftlichste Nutzung ausrichtet und z B zur Wohnungssteuerung angewandt wird Die EIN AUS Regelung ist eine herk mmliche Differenzregelform z B...

Page 8: ...r kurzgeschlossen Klemme 10 11 F hler F hlerkabel austau schen F r fortgesetzten Betrieb ohne F hler kann der Thermos tat auf Regler unter Anwendung APp a C eingestellt werden E2 Externer Boden f hler...

Page 9: ...ectronics A S 9 MCS4 10 MSD4 1999 MSA4 10 ETN4 1999 9 9 9 9 10 10 9 10 10 10 10 10 10 10 10 10 11 11 11 11 11 11 11 EN50559 12 12 12 12 ETN4 1999 DIN 19 5 70 C C I 0 0 30 19 5 70 C SCA a Hi Lo Li a Hi...

Page 10: ...5 C 19 5 60 C 1 Li a Hi a 28 28 C 19 5 70 C 1 Li a Lo a 15 15 C 19 5 70 C 2 Li a Lo a 19 5 19 5 C 19 5 70 C dEF a 8 0 8 C 0 10 C 3 nSb a 5 0 5 C 19 5 30 C FLo a 24 5 4 ro a 21 5 4 APp a F a A a Li a A...

Page 11: ...11 Li Li a Lo Li APp Li a Lo Li a Lo Lo APp a Li AF C APp a C Night setback 20 60 25 0 60 x 0 25 0 15 15 nSb nSb APp C 100 ETN4 1999 20 100 nSb nSb nSb nSb 30 nSb dEF nSb 0 0 10 0 0 0 SCA aLo 10 0 SC...

Page 12: ...3 12 13 14 Fax 45 73 12 13 13 oj ojelectronics com www ojelectronics com 12 EN50559 EN 50559 VDE 0705 559 4 EN DIN 0 20 90 10 10 6 10 EN50559 6 EN50559 2 2 1 60 10 APp aF ETN4 1999 OJ Electronics A S...

Page 13: ...is boutons de navigation permettent une utilisation ais e du menu FONCTIONNEMENT G N RAL Bouton central Programmation Interrupteur ON OFF Bouton de gauche Temp rature plus basse Bouton droit Augmenter...

Page 14: ...e Affiche la temp rature ambiante r elle Application R gle la fonction du thermostat S lectionnez le type de contr le requis Remarque Sonde d ambiance non utilis e Plancher F Le thermostat contr le un...

Page 15: ...st activ e La zone gris clair correspond la dur e de fonctionnement relative lorsque la fonction nocturne a t activ e par les valeurs susmen tionn es La valeur par d faut du degr de la fonction noctur...

Page 16: ...du thermostat Appuyez sur le bouton central et maintenez le enfonc pendant 10 secondes L cran est teint puis rallum L application est affich e l cran APp aF suivi du r glage de la temp rature ETN4 19...

Reviews: