I N S T R U C T I O N S

 © 2016 OJ Electronics A/S

1

67025D 07/16 (LOA)

Type OSD4-1999

English

CS4

TM

 THERMOSTAT

A wireless, radio controlled thermostat recom-

mended for Comfort System 4. The thermostat is 

ideal for all floor types and controls the heating 

on the basis of room, floor or room/floor limit 

temperature. Wireless communication to the cen-

tral controller ensures easy installation.

PRODUCT PROGRAMME

OSD4-1999  Radio controlled thermostat with 

built-in room sensor and floor sensor

WARNING

 – Important Safety Instructions 

Disconnect the power supply before carrying out 

any installation or maintenance work on this unit 

and associated components. This unit and as-

sociated components should only be installed by 

a competent person (i.e. a qualified electrician). 

Electrical installation must be in accordance with 

appropriate statutory regulations.

INSTALLING THE THERMOSTAT 

The thermostat is for flush mounting in a wall 

socket. A baseplate for external wall mounting is 

available.

Fig. 1:

1.  Slide the power button down to Off “0”.

2.  Release the front cover ONLY by inserting a 

small screwdriver into the hole on either side 

of the thermostat.

Fig. 2 + 2a:

3.  Connect the wires in accordance with the 

diagram. 

4.  Mount the thermostat in the wall socket. 

5.  Fit the frame and carefully press the cover 

onto the thermostat. Ensure that both the 

power slide button on the cover and the 

power switch pin are down.

DO NOT

 open the thermostat by releasing the 

four fixing clips on the back.

MOUNTING OF SENSOR

The terminals for the sensors contain a safety 

extra-low voltage (SELV) circuit, allowing the 

sensors to be placed as close to the floor surface 

as necessary without the risk of electric shock, 

should the sensor cable become damaged. 

Sensor cable recommendations

•  The sensor cable may be extended up to 30 m 

by means of a separate two-core cable.

•  The two wires from the sensor to the thermo-

stat must be kept separate from high voltage 

wires/cables. 

Place the cable in a separate pipe or segre-

gate it from power cables in som other way.  

Never use two vacant wires in a multi-core 

cable.

•  Shielded cable: Do not connect the shield to 

earth (PE).

 

Fig. 3: Mounting of floor sensor

The floor sensor is used for comfort temperature 

regulation in rooms on the basis of floor tem-

perature. It is recommended that the cable and 

sensor be placed in a non-conductive installation 

pipe embedded in the floor. The end of the pipe 

must be sealed and the pipe placed as high as 

possible in the concrete layer.   

The floor sensor must be centred between loops 

of heating cable. 

PLACING THE THERMOSTAT

The room sensor is used for comfort temperature 

regulation in rooms. 

Fig. 4:

The thermostat should be mounted on the wall 

approx. 1.6 m above the floor in such a way as to 

allow free air circulation around it. The thermostat 

must never be covered by a curtain or similar.

Draughts and direct sunlight or other heat 

sources must be avoided. 

Fig. 4a:

Observe the minimum distance of 0,5m, from 

large metal surfaces, electronic equipment, 

electric motors, etc.

Fig. 4b:

To ensure good wireless transmission without 

interference, 

all wireless units

 in the Comfort 

System CS4

TM

 should always be placed with 

min. 1,0m between them.

QUICK SETUP

Quick guide to thermostat setup:

1. Activate the Central Controller.  

Go to Menu/System settings.

2. Select Add unit.

3. Activate the thermostat.  

The address will be displayed.

4. Select time schedule in the 

menu of the central controller. 

You need to name the time 

schedules from the list (zone-

names). You can max. have 5 

time schedules in the system.

PROGRAMMING 

See user manual for CS4

TM

 for further options 

and how to plan you system

FIG.5: SENSOR RESISTANCE

If the sensor is disconnected or short-circuited, 

the heating system is switched off. The sensor 

can be checked against the resistance table.

ERROR CODES / STATUS

E0: Internal error. The unit must be replaced.

E1:  Built-in sensor short-circuited or discon-

nected.

E2:  External sensor short-circuited or discon-

nected.

E5:  Internal overheating. Inspect the installation.

E8:  Wrong application in the thermostat or the 

time schedule.

   Communication error. No connection to the 

central controller - The thermostat will switch 

to manual mode.

 

 The aerial strenght to the Central Controller is 

displayed in 1 to 4 bars. 4=Full signal, 1=very 

low signal.

FACTORY RESET

Allows factory settings to be restored. Your 

personal settings will be lost for this thermostat, 

and the connection to the central controller will 

be interupted.

1. Press and hold the middle button until the 

display stops flashing and the manual symbol 

Systemsettings

Add to unit

is shown (after 10 seconds). 

The factory settings are now restored and the 

thermostat is in manual mode.

2. Turn the thermostat OFF and back ON to 

reconnect to the Central Controller.

CERTIFICATION

OJ Electronics A/S hereby declares that  

the product conforms with the following 

Directives of the European Parliament 

and of the Council: 

LVD, EMC, R&TTE, RoHS and WEEE 

Applied standards

Please see the document “EC DECLARATION 

OF CONFORMITY” in the back.

CLASSIFICATION

The product is a Class II device (enhanced 

insulation) and must be connected in the follow-

ing way: 

Term. 1:   Neutral (N)

Term. 2:   Phase (L) 230 V ±10 %, 50/60 Hz 

Term. 3-4:  Load, max. 16 A / 3600 W

Term. X:   Do not connect

Term. 5-6:  External floor sensor

ENVIRONMENT AND RECYCLING

Please help us to protect the environment by 

disposing of the packaging in accordance with 

national regulations for waste processing.

RECYCLING OF OBSOLETE APPLIANCES

Appliances with this label must 

not be disposed of with general 

household waste. They must be col-

lected separately and disposed of in 

compliance with local regulations.

 

TECHNICAL DATA

Voltage  ........................... 230 V AC ±10 % 50 Hz

Max. pre-fuse ................................................. 16 A

Built-in circuit breaker ....................... 2-pole, 16 A

Output relay............... Make contact - SPST - NO

Output ....................................... Max. 16 A / 3600

Control principle ......................................  PWM/PI

Stand-by power .............................................  1 W

RF frequency band .............................. 868.3 Mhz

RF transmission range .......100 metres/open field 

Temperature range ................................+5/+40 °C

Limit sensor  ..........................................+5/+40 °C

Ambient operating temperature ............+0/+25 °C

Sensor input type ..........................................SELV

Pollution degree .................................................. 2

Overvoltage ..................................................Cat. II

Rated impulse voltage ..................................  4 kV

Enclosure rating .......................................... IP 21*

Dimensions ....................... H/81, W/81, D/40 mm

Mounting depth .........................................  20 mm

Display .......................... H/25, W48 mm, segment

EU Registered Design  ..........  001534462-0001/2

According to EN 60730-1:2011

Automatic action type 1 

* IP 21 applies only to front with cover after 

mounting in a flush box

The thermostat is maintenance free.