INSTRUCTIONS
Master with Display type WlM2
introduction
The masters type WLM2-1bA and
-3bA are pre-set and need no
adustment. See Master factory
settings page 11.
WLM2-1BA - 3BA
WLM2-1FS -3FS
Using Clock thermostat (WLCT2-x9):
If a room controller is used as an area control for one room or a group of rooms, then all the room
sensors within this zone will operate according to the temperatures and times defined in the room
controller. However the local room sensors within the group are still capable of being adjusted by
± 4˚C so that some rooms can be set higher or lower than others. The decision as to which room
sensors will form part of the room controllers group is made by programming the room controller
(see instructions for WLCT2 unit). Any room sensors that are not part of the room controllers
group will operate to the temperature as defined in the master control, but again with the option of
local ±4˚C adjustment.
Using External Switch for Night Setback
The day temperature set point is defaulted to typically 21˚C and the night temperature to
typically 18˚C. These default settings can be changed on the FS master.
The current operating set point of the master can be changed from the day temperature into
night temperature, by connecting a separate timing device to the master. When the external
switch or timer is used to switch to night setback, this will override any time settings in a
WLCT2 room controller, including any room sensors that are part of a group allocated to that
room controller.
The masters type WLM2-1FS and
WLM2-3FS are provided with graphic
display to enable simple programming
and operations of the unit to be
achieved using simple and easy to
understand icons and symbols.
The ADD ON type WLM2-1AO
and WLM2-3AO is an extension
module for additional 6 outputs.
The module needs no adjustment
WLM2-1AO and WLM2-3AO