16
Err
or Indication
Flashing output LED (red):
The appropriate output channel LED can fl ash, indicating that the room sensor or room contoller on that channel has a fault/error. The failure code can
also be seen in the service menu (submenu 2a).
E1, 1 fl ash
The master has lost communication to the room sensor. The fault is corrected by re-establishing the connection to the Room
Sensor and the fault condition will be automatically reset once correct communication is resumed. If the room sensor is
defective and has to be changed, or if it has been deliberately removed, it is necessary to make a HARD RESET. (NOTE: If the
room sensor is of the WIRELESS type, the error/fault message could be an indication that the power has failed, and that the
internal battery of the room sensor needs to be replaced)
E2, 2 fl ashes
The internal sensor in the room sensor/controller is defective. The fault can only be corrected by replacing the room sensor/
Controller. Remember to make a HARD RESET after installing the new room sensor/controller.
E3, 3 fl ashes
The limit sensor on the room sensor/controller is defective. Replace the faulty sensor. Reset is NOT required.
E4, 4 fl ashes
Defective WLCT2 room controller. If a room controller operating a group of room sensors becomes defective, the remaining
room sensors will continue control within the maximum and minimum limits programmed into the Room controller.
E5, 5 fl ashes
Two or more room controllers are trying to control this output. Check “AREA” setting on the room controllers.
E6, 6 fl ashes Channel output number one is confi gured as a dehumidifi er output, error caused by a room sensor/controller also being set to
control this output.
RESET
There are 2 different reset actions that can be used.
HARD RESET
If the ‘
✓
’ button is pressed for 5 seconds, a HARD RESET will be initiated. (Indicated by all the red output LED’s(1-8) lighting in sequence). This reset
will remove from the system any room sensor unit with a defective input sensor, or a defective AO module. The fault message will be reset but the
defective items will no longer participate in the system. To add or replace a new unit, please refer to “Replacing equipment - Replacing a faulty sensor/
controller”. To erase the identity of the defective component from the master memory a HARD RESET must be performed Hard resets do not alter the
temperature settings already programmed into the master control.
FACTORY RESET
If the (
√
) button is pressed for more than 15 seconds, a total factory reset will be initiated. This is indicated through fl ashes of channel LEDs 1,3, 5 and
7 alternating with channel LEDs 2, 4, 6 and 8 (while the “
√
” button is pressed).
A factory reset will put all programmed temperature settings back to the factory defaults. It will also remove all room sensors/Controllers from the
master memory, and reset the system to accept only those room sensors/Controllers that are functioning correctly.
To reconnect room sensors/controllers, please refer to “Replacing equipment - Replacing a faulty sensor/controller”.