23

T

ype WLCT2

 (and WLCT2/R/HW/2)

Hi Li - Floor sensor. Max and min allowed temperature of the fl oor surface

A limit sensor can be connected to the room controller.

Max limitation

 is used for safety to prevent high fl oor temperatures. For example wooden fl oor constructions which should not 

be allowed to exceed a maximum of 27˚C. The value can be set from 5˚C up to 55˚C. The value can also be set to OFF (adjust the 
temperature to 55˚C and push button up once more).

Low limitation

 is used where the temperature of the fl oor is required never to fall below the minimum set temperature. Example in 

kitchens or bathrooms with tiles. The value can be set from 5˚C up to 55˚C. The value can also be set to OFF (adjust the temperature to 
5˚C and push button down once more). Remember the max limit temperature must be set higher than the min limit temperature.
The limit temperatures defi ned in the room controller will be valid for all the room sensors with limit sensor (type WLTD-19) which are part 
of the area allocated to the WLCT2 unit.

The maximum allowable fl oor temperature setting is shown. Use 
the UP (

) or DOWN (

) button to increase or reduce, and OK (   ) 

button to accept.

The display will now show LoLi. Press OK (   ) button to continue.

The minimum allowable fl oor temperature setting. Use the UP (

or DOWN (

) button to increase or reduce and OK (   ) button to 

accept.

SCAL - Time and temperature scale selection

You can select either ˚C or ˚F scale, and 12 or 24 hour clock as 
follows:

Press UP (

) or DOWN (

) button to change settings. Confi rm the 

required scale with the OK button (   ) button.

ArEA - (Group of rooms)

The  rooms that are to be set as part of the WLCT2 area will follow the temperature settings of the room controller example, an area could 
be the living room, kitchen, and children’s rooms, having a high room temperature requirement during afternoon and early evening, and 
a lower temperature during the early part of the day and at night. Each room sensor will have a channel number, designated CH1, CH2 
etc. The appropriate channel number of any room sensor is determined by the numbered output on the master control which is actually 
switching the valve/actuator for that area.

For example, a system may have the kitchen room sensor operating master output # 4, and the childrens room sensor operating 
master output #5. If the WLCT2 room controller is then situated in the living room, and operating output #1, then the WLCT2 need 
be programmed to control outputs 1, 4, & 5. (Each room sensor will have been set to operate its appropriate output ch see separate 
instructions).
To do this, enter the ArEA sub menu., and press OK ( ) button. CH 1 will be displayed; use the OK  ( ) button and then the UP (

) button 

to change the setting to ON. Press OK ( ) and CH 2 is displayed. Use the UP (

) button until CH4 is displayed, press OK ( ), and change 

to ON. Repeat this for CH 5. All three room sensors will now operate under the control of the WLCT2 room controller.

In total up to 14 Channels can be programmed in this way, and it is possible to have more than a single room controller, each own sub 
room sensors operating to its schedule and temperatures.

Summary of Contents for WLM2

Page 1: ...www oj dk User Manual WLM2 WLTA WLTD WLTP WLCT2 57640A 11 08 DJU...

Page 2: ...rature and mixing devices This ensures the best possible comfort conditions and also reduces energy consumption Highlights of the system depending on equipment Heating and cooling control for true com...

Page 3: ...sation 9 Service Menu 11 Using cooling functions 13 Master Factory Settings 13 Error Indication 15 Type WLCT2 and WLCT2 R HW 2 17 Introduction 17 Getting Started 17 Daily Use of the room sensor 20 Pro...

Page 4: ...ows CH 1 channel 1 Press OK button These room sensors have an adjustment knob which enables you to increase or decrease the room temperature setting by up to 4 C room sensors type WLTM 19 and WLTD 19...

Page 5: ...press OK NB If different times and temperatures are required for other channels room sensors within the system more than one WLCT2 room controller can be used Care must be taken to ensure that the act...

Page 6: ...ion For rooms with floor sensors the maximum floor limit setting could be preventing the room reaching the desired temperature Insufficient heating capacity of the system Bad insulation creating large...

Page 7: ...the temperature as defined in the master control but again with the option of local 4 C adjustment Using External Switch for Night Setback The day temperature set point is defaulted to typically 21 C...

Page 8: ...n the master module Maximum Floor limit temperature for room sensors with limit sensor floor sensor Minimum Floor limit temperature for room sensors with limit sensor floor sensor Max Min By using the...

Page 9: ...ill vary depending on the outdoor temperature and the room temperature requirements of the system For example on a day when the outdoor temperature is 12 C it is possible to run the heating system wit...

Page 10: ...efault setting is 20 C Then set the supply water temperature that you require when the outside temperature is at 20 C The default is 25 C To start the summer shut down at a lower temperature level red...

Page 11: ...IDxx Shows if any of the attached masters has local errors IDxx tells which master it concerns The ID number is what the encoder on the master is set to NET ERROR Tells that one or more masters on the...

Page 12: ...mixing valve At 10 V the mixing valve is fully open unless the output setting has been changed to 10 0 in which case at 10 V the valve will be fully closed 24 0 C 22 9 C Read out Room temperature in...

Page 13: ...midity sensor the system limits the formation of condensation on floor surfaces due to high humidity If a dehumidifier is being used it will activate if high humidity limits the cooling function When...

Page 14: ...180 sec K factor 0 1 Floor Limit temperature control P control P 4 C Adaptive PWM control Max allowed Room temperature fluctuation 0 5 C Self adjusting adaptive PWM time interval limits 15 45 minutes...

Page 15: ...ng the channel number of the room sensor to a channel that does exist within the installed master add on module system E3 3 flashes Application sensor defect The fault is corrected by changing the tem...

Page 16: ...hes Two or more room controllers are trying to control this output Check AREA setting on the room controllers E6 6 flashes Channel output number one is configured as a dehumidifier output error caused...

Page 17: ...operate from the WLCT2 x9 settings e g A WLCT2 x9 is set to 22 C and has been given control over Area 1 the WLTA x9 fitted in Area 1 now has a control range of 18 C 4 C to 24 C 4 C In addition to the...

Page 18: ...ill be flashing and must be set If you need to adjust the time of the thermostat at a later date insert a pin into the hole marked see fig 1 for setting of time and day Adjustment should be made for c...

Page 19: ...master output 5 If the WLCT2 room controller is then situated in the living room and operating output 1 then the WLCT2 need be programmed to control outputs 1 4 5 Each room sensor will have been set...

Page 20: ...ge 17 Comfort mode 5 secs Temporary override To temporarily override any temperature in the 4 event schedule program press the UP button once to show the temperature in the display and press UP or DOW...

Page 21: ...the second third and fourth event These settings will be valid for days 1 5 showing on the display To program the days 6 and 7 repeat the above Days 6 and 7 are usually Saturday and Sunday and only ha...

Page 22: ...ress UP or DOWN button to show the different readouts No changes can be made here Use the OK button to end PRO 4 event sequence It is possible to change the factory event sequence of Days 1 5 4 event...

Page 23: ...ck as follows Press UP or DOWN button to change settings Confirm the required scale with the OK button button ArEA Group of rooms The rooms that are to be set as part of the WLCT2 area will follow the...

Page 24: ...ess OK to continue Use the UP or DOWN button to change the temperature setpoint in the 2 step function If the actual room temperature is higher than the setpoint minus this setting the second output w...

Page 25: ...herefore the thermostat may switch ON as early as 06 00 so that the desired temperature of 2 5 C is achieved by 07 00 Without this function set the thermostat will start to heat at the time you set Pr...

Page 26: ...On Ch 2 Living room On 4 event time and temperature Own settings Standard WLCT2 x9 Special WLCT2 x9 R Special WLCT2 x9 2 Special WLCT2 9 HW Time Temperature Temperature Temperature Temperature Time Te...

Page 27: ...9 R by using the up or down button The 4 event system in the WLCT2 X9 R can be used to save energy when heat is not needed 2 step heating A special version of the WLCT2 called WLCT2 X9 2 is capable of...

Page 28: ...vice to the master or using a WLCT2 Room controller and allocating other Room sensors as part of its group It is possible to have two or more Room controllers in the system with each one having its ow...

Page 29: ...WWW OJ DK OJ ELECTRONICS UK CRUSADER PARK WARMINSTER WILTSHIRE BA12 8SP UNITED KINGDOM T 44 01985 213 003 F 44 01985 213 310 SALES OJUK CO UK WWW OJUK CO UK OJ ELECTRONICS A S C O ROBERT BIELECKI UL...

Page 30: ...LEAVE THIS INSTRUCTION WITH THE CLIENT NB Thermostats Thermo heads Output Zone Water loops Thermostats CH 1 1 CH 2 2 CH 3 3 CH 4 4 CH 5 5 CH 6 6 CH 7 7 CH 8 8 CH 9 9 CH A 10 CH B 11 CH C 12 CH D 13 C...

Reviews: