Outdoor Compensation Module- T
ype WLOC-19
Introduction
The masters WLM2-1FS and WLM2-3FS are supplied already prepared for weather compensation
and simply by adding the outdoor compensation module on the 2-wire bus and using the water
temperature sensor on the supply water side, you have a control system for weather compensation.
Preset values are programmed at the factory, but these values can easily be adjusted according to
local needs via the display on the master. See the user manual ”Master with display type WLM” for
changing of the default factory settings
Mounting
The outdoor compensation module is mounted under the roof eaves, alternative 2-3 m above ground
level. Direct sunlight or any other direct heating source such as air ventilation must be avoided. The
outdoor compensation module is mounted vertically with the cable entry downwards.
BUS CONNECTION - Outdoor Compensation Module
Only OJ Outdoor Compensation Modules type WLOC-19 that are prepared for 2 wire
communication can be used.
Standard installation cable, minimum 2 x0.25 mm2 can be used. The outdoor compensation module
can be connected in the conventional star wiring format, or in a bus connected mode (Daisy chain).
The master has 4 sets of terminals marked Room sensor BUS that can be used for connecting the
2-wire signal from the Room sensors and the outdoor compensation module.
There are 4 identical sets of terminals for convenient installation. Any Room sensor / outdoor
compensation module can be connected to any pair of terminals. The total length of the 2-wire
system can be up to 300 m with a maximum length of 100 m between any 2 Room sensors / outdoor
compensation module. Remember to c to + and - to -.
Outdoor Compensation Module- Type WLOC-19
INSTRUCTIONS
Interconnection of WLM2 products:
For easy installation, interconnections between master modules, master and add on modules, and
master and wireless receivers, are made by pre-wired plug in connectors (RJ45) For connecting
WLM2 add on modules to WLM2 masters, a plug in connector is provided with the add on module.
A WLRC wireless receiver is also connected to a WLM2 master, using the plug in connector provided
with the receiver.
For connecting a WLM2 master to another master, a plug in connector kit is available.