Output Test
131
Designation
Check if
If not, then check
Note:
only possible if the boiler control-
led pump is connected
Motor store room
auger
RA
the motor auger store room is running
Note:
On suction systems, switch on the
suction fan motor first otherwise
the motor on the store room auger
may become jammed.
• the store room auger motor is connected
• the auger rotates easily
• the motor is defective
Motor hopper
RES 1
Note:
PES 36–56 only
• the wiring is correct
• the motor is defective
Motor burner
auger
ES
• the motor that feeds pellets to the
burner is running auger is correct.
• the direction of rotation of the store
room auger is correct
• the burner auger motor is connected
• the burner auger motor rotates easily
• the motor is defective
Combustion air
fan
LUFT
The combustion air fan is running
• the wiring is correct
• the motor is defective
Anti-blowback
system
BSK
the fire protection flap (orange motor
on burner) opens
• the wiring is correct
• the ball valve moves easily
• the motor is defective
Scrubber pump
Note:
not implemented at this type of
boiler
• the wiring is correct
• the scrubber pump is defective
Operating Manual PELLEMATIC® PE(S)(K)(B) 10 — 56
Summary of Contents for PE 08
Page 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Page 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Page 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Page 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Page 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Page 168: ......
Page 169: ......