Malfunction report
159
13.1b Sensors KTY2K - Heating cont Boiler Controller (Fault 2001 to 2020 and 5000 bis 5007) –
short circuit
Type of fault
Short circuit
Code :
2001
HC1 Flow SC
X4
2002
DHW1 OnSensor SC
X6
2003
Outside Sensor SC
X2
2004
Boiler Sensor SC
X3
2008
TPO1 SC
X7
2009
TPM1 SC
X8
2011
TPU1 SC
X9
2012
Flow Energy1 SC
X16
2013
Return Energy 1 SC
X17
2014
ExistBoiler1 SC
X13
2017
Cascade OnSensor SC
X3
2018
Sonde arrêt cascade CC
X3
2019
Circulation Return1 SC
X14
2020
WW1 Aus Fühler KS
X6
5001
PE1 Reserve sensor1 SC
R1
5003
PE1 Reserve sensor2 SC
R2
5005
PE1 Outside sensor SC
AF
5007
PE1 Boiler sensor SC
KF
Description:
Measuring circuit of KTY sensor is shorted out
Cause and Remedy:
Sensor defect
ڃ
Measure sensor (approx. 2k
ˑ
at 25°C), replace if required
Sensor cable defect
ڃ
Replace sensor
Sensor temperature too low
ڃ
Sensor temperature below
measuring range (<-10°C)
Operating Manual PELLEMATIC® PE(S)(K)(B) 10 — 56
Summary of Contents for PE 08
Page 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Page 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Page 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Page 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Page 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Page 168: ......
Page 169: ......