Malfunction report
161
13.3 Bus (Fault 4005, 4006, 4007, 4015, 4016)
Display:
[4005] BUS HCR
Description:
Time-Out of BUS-connection from touch operating device to heating
controller
Cause and Remedy:
Wrong cable connection
ڃ
Check cable connection
No power supply available
ڃ
Connect heating controller to BUS
Fuse in heating controller
defect
ڃ
Replace fuse
Display:
[4006] BUS PE
Description:
Time-Out of BUS-connection from touch operating device to boiler controller
Cause and Remedy:
Wrong cable connection
ڃ
Check cable connection
No power supply available
ڃ
Connect heating controller to power supply
(X21)
Fuse in heating F2 defect
ڃ
Replace fuse F2
Display:
[4007] BUS Remote
Description:
Time-Out of BUS-connection of remote control
Cause and Remedy:
Wrong cable connection
ڃ
Check cable connection
Remote controll defect
ڃ
Replace remote controll
Display:
[4015] BUS Remote Touch
Description:
Time-Out of BUS-Connection from remote controll to Touch operating device
Cause and Remedy:
Wrong cable connection
ڃ
Check cable connection
Wrong softwareversion
ڃ
Check version of software
Display:
[4016] BUS Master
Description:
Missing BUS connection to master-operating device
Cause and Remedy:
Wrong cable connection
ڃ
Check cable connection
13.4 Combustion chamber sensor (Fault 5010, 5011, 5048, 5049)
Display:
[5010] PE Combustion sensor BS
Description:
Combustion chamber sensor fracture, measuring circuit from combustion
chamber sensor is open – Input FRT
Cause and Remedy:
Sensor not connected
ڃ
Connect sensor at input
Sensor defect
ڃ
Measure sensor (approx. 5 mV at 125°C) re-
place if required
Sensor cable defect
ڃ
Replace sensor
Sensor temperature too
high
ڃ
Sensor temperature above measuring range
(1100°C)
Display:
[5011] PE Combustion sensor SC
Description:
Combustion chamber sensor short circuit, measuring circuit from combustion
chamber sensor short circuit – Input FRT
Operating Manual PELLEMATIC® PE(S)(K)(B) 10 — 56
Summary of Contents for PE 08
Page 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Page 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Page 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Page 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Page 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Page 168: ......
Page 169: ......