Page 28
Should a channel be deactivated, the measured signal is no longer
evaluated.
Alarm and fault conditions on the deactivated channel will not be
signalled. The corresponding LEDs and relay will not be activated.
Channel deactivation will be extant even after the service mode is closed.
The channel can be re-activated by renewed selection.
ATTENTION!
Even if the channel is switched off, the detector will be powered with 24 V. For
works to be carried out in hazardous areas, power to the detector must be
disconnected.
For safety reasons, an alarm is internally signaled when deactivating a channel
being in an AND or VOTING operation. The alarm will, however, not be shown
on the LED module. This evaluation may cause alarm signaling with an AND or
VOTING operation of channels, even though this should not be the case
according to the displays of the LED modules.
Display, messages, outputs:
LED module:
all LEDs for deactivated channels are off
System:
LED
Service
is on, the relay
Service
is activated when
switch in position 4 and one channel is deac tivated or
even selected for deactivation
RBM/REM:
all corresponding relays are deactivated
AAM:
2 mA or 0 V
LCD module:
deactivated channel is not displayed
Printer:
message:
Service relay activated
3.4.5.
PC communication (switch position 5)
PC communication allows external access to the system WinPro
®
/ MX62,
e.g. for changing the configuration with software
ConfigPro
.
Measurement and evaluation are continued as long as no command via PC
communication is given that requires quitting the measuring mode.
During UPLOAD (see operation manualfor software ConfigPro) of
a changed system configuration, first of all an alarm for system
error is triggered. After resetting, the system will be re-started with
the changed configuration (see chapter 3.2).
Display, messages, outputs:
LED module:
as operation status
System:
LED
Service
is on, the relay
Service
is activated when
a PC is logged
RBM/REM:
as operation status
Summary of Contents for MX62
Page 2: ...Subject to change without notice FE BA WinPro MX 62 R6 GB 1604CBR...
Page 4: ...Page 4...
Page 10: ...Page 10...
Page 18: ...Page 18...
Page 58: ...Page 58...
Page 60: ...Page 60...
Page 64: ...Page 64...
Page 65: ...Page 65 12 EU declaration of conformity...
Page 66: ...Page 66...
Page 68: ...Page 68...