Page 47
DH1 BASE UNIT / DH2 WIRELESS GATEWAY
USER GUIDE
24.
MODBUS WRITE FUNCTION AND WRITING TO
GATEWAY
In order to relay data from a third-party Modbus Master device to a point
or output in an OleumTech network, a Modbus Write function must be
created in primary Gateway’s Modbus table. Once the function is created,
then this point can be mapped to an output or shared with another device
within the network.
A Master device connected to the Gateway have access to write to the
same Modbus holding register(s). Last written command supersedes all
other commands.
Gateway must be set up as a Slave to allow this function.
1.
Double-click on Gateway in project tree
2.
Click on Modbus tab
3.
Right-click inside Modbus window and select “New Write Import”
4.
Provide a Name for the function and select point as an integer or
float point
Controlled Copy