6.  STARTING AND PROGRAMMING 

 

The  starting  and  programming  operations  must  be  executed  exclusively  by  experienced  and 
qualified  staff.  Use  the  appropriate  equipment  and  protections.  To  supply  voltage  on  the 
Inverter verify that the Inverter box is completely closed, after having carefully followed all the 
instructions wiring above. 

 

   

The  pump  can  not  run  dry;  functioning  under  these  conditions  (even  for  a  short  time)  irreparably  damage  the 
pump itself. For this the control system intervenes after about a minute (usually sufficient time for water loading 
pump during the initial service) with an alarm, stopping the pump as described in Chapter 2. 
Make the air purging on the pump.To prevent the entry of impurity in the first  put in service, in case of pumping 
of drinking water, run an abundant rinsing and disinfecting. 

 

 
The motor, can reach temperatures above 100 ¡C. Danger of burns to simple contact with the 
motor. 
 

 

6.1  First Inverter Using – Self Regulation procedure 

 

·

 

Press START and set the 

nominal current

 

absorbing

 for the phases connection in use (see 5.3); 

·

 

Press START and on 

rotation direction

 request, maintaining pulsed the START button until the reading of 

electrical  data  measures  and  select  the  direction  (0,1)  with  Ò+Ó  and  Ò-Ò  buttons,  finally  confirming  with 
ENTER.  

·

 

Be sure that the pump is fully of water and 

close completely the outlet of the pump

.  

·

 

Pressing  START  for  the  Self-Regulation  Check  for  the  registration  of  the  curve  of  the  pump  for  the 
regulation of the stop for closed output. During the Check the display show ÒEXECUTING CHECKÓ; at the 
end of the check the Inverter automatically save data and the pump may work normally. 

 

during  Self-regulation  Check  the  pump  may  arrive  at  the  nominal  velocity,  with  maximum 
pressure. If you need, limits the maximum pressure previously (Pump Data).  

 

 

 

6.2  User’s check after Inverter setting 

 

Check  the  pump  stop  for  Minimum  Flow

:  At  the  first  installation  open  the  output  on  the  pump  flow,  press 

START, wait a few seconds for the plant go to pressure set, then close the output flow (slowly) and make sure 
that the motor stops (after a few seconds) showing on display "MINIMUM FLOW". In case the motor does not 
stop you must select MOTOR DATA - POWER STOP and set a higher value than the default (103%) set by the 
constructor. The absolute stop power value is showed at regular times on display at the top-central position (see 
fig. 10).  

 

Check  pump  dry-working

:  After  installation,  if  itÕs  possible,  close  the  suction/intake  of  pump  in  order  to 

simulate  a  run  dry  situation;  After  a  time  of  about  40  seconds  (or  the  set  delay  time),  the  pump  should  stop, 
displaying  ÒDRY  WORKING".  If,  after  this  time,  the  pump  does  not  stop  you  must  set  into  ADVANCED 
FUNCTIONS Ð PRESSURE CONTROL setting a higher value of the parameter COSFI LIMIT (by default set to 
0.5). Save data after modifying. 

 

 
 
 
 
 
 
 
 
 

Summary of Contents for IMTP 2.2 M-RS

Page 1: ...Motor Pump Inverter Type IMTP 2 2 M RS ITTP 2 2 M RS ITTP 4 M W RS ITTP 5 5 M W RS ITTP 7 5 W RS ENG Operation and maintenance handbook...

Page 2: ...5 Electric connection to Line and Motor 7 5 6 Pressure transducer connection on different types 8 5 7 Connections on the electronic board 9 6 STARTING AND PROGRAMMING 12 6 1 First Inverter Using Self...

Page 3: ...0mA or 0 5V output The control logic works with an output of 5 or 15V switchable that supplies the pressure transducer MINIMUM FLOW WORKING PROTECTION to prevent a closed delivery working the control...

Page 4: ...ty regulations could endangers others and damage the devices which can lead to loss of warranty The results of the non observance of the security rules can be Malfunctioning of the system Danger to ot...

Page 5: ...to remove the paint from the contact surface It is necessary to avoid ground loop that is like an antenna for EMC emission Power supply must be admitted on working condition don t lift or carry the m...

Page 6: ...ic system Before working be certain all the circuit is without voltage also the connections voltage clear Disconnect the inverter from the power supply before working on electrical or mechanical parts...

Page 7: ...wo cables connectors from the logic board J1 26 poles e J2 4 poles for IMTP2 2 ITTP2 2 Figure 5 or J5 26 poles for ITTP4 7 5 Figure 8 Connect the 3 motor terminals U V W on the power board on IMTP2 2...

Page 8: ...nnectors for IMTP ITTP2 2 fig 5 and J9 for ITTP4 7 5 fig 8 if previously disconnected making sure they are firmly fixed don t forget the clamp on J9 for ITTP4 7 5 fig 8 Replace and close the box using...

Page 9: ...9 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG 5 7 Connections on the electronic board Figure 5 Logic board of IMTP2 2 ITTP 2 2...

Page 10: ...10 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 6 Power board of IMTP 2 2 Figure 7 Power board of ITTP 2 2...

Page 11: ...11 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 8 Logic board of ITTP 4 7 5 Figure 9 Power board of ITTP 4 7 5...

Page 12: ...pump is fully of water and close completely the outlet of the pump Pressing START for the Self Regulation Check for the registration of the curve of the pump for the regulation of the stop for closed...

Page 13: ...after the variation press ENTER Decrease the reference pressure during functioning ESC To exit to the function and automatically saving START Pump start STOP Pump stop If pressed with the key during...

Page 14: ...iangle see 5 3 Set the rotation direction 0 1 Default 0 Regulation of the minimum flow power for the motor stop in closed output condition Regulation of the dry working power stop default 80 Pump data...

Page 15: ...flow stop Default 12 second 15 second for ITTP4 7 5 4 Re start delay time after minimum flow stop Default 1 second 5 Dry working stop delay time for pump filling Default 40 seconds 6 When cos go down...

Page 16: ...faulty current control Automatic re start final stop after 10 consecutive events 13 Input Voltage under limit Input voltage under the minimum working limit Automatic re start final stop after 10 cons...

Page 17: ...output power to the motor then stop the motor and the inverter show Over Temperature IGBT alarm Inverter Temperature alarm Temperature of the electronic board of the inverter is too high and the inve...

Page 18: ...at pump haven t any defect fault seal impellers etc that can cause a big power absorbing also without water in dry condition 13 A group of two or more inverters cannot communicate between each other i...

Page 19: ...ctives and to national law following the technical standards Machines 98 37 CE Low Voltage 73 23 CE e successive modifiche and subsequent amendments IEC EN 61000 6 1 CEI EN 61000 6 4 ETSI EN 301 489 1...

Page 20: ...na Ind Esmoriz Sector C 8 36 13 86 O GPS OLIJU Manufacturing 40 57 27 11 N PORTUGAL PORTUGAL 4520 475 Rio Me o Zona Industrial de Rio Me o Avenida Santiago N 43 40 57 37 20 N 8 35 50 10 O GPS OLIJU Co...

Reviews: